Worked example
Example: Typical branch at 8 m/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air velocity | 8.0000 m/s |
| Air density | 1.2000 kg/m³ |
| Fitting 1: loss coefficient | 0.25000 - |
| Fitting 1: number | 4.0000 - |
| Fitting 2: loss coefficient | 0.60000 - |
| Fitting 2: number | 2.0000 - |
| Fitting 3: loss coefficient | 1.0000 - |
| Fitting 3: number | 1.0000 - |
| Fitting 4: loss coefficient | 0.30000 - |
| Fitting 4: number | 2.0000 - |
| Fitting 5: loss coefficient | 0 - |
| Fitting 5: number | 0 - |
| Fitting 6: loss coefficient | 0 - |
| Fitting 6: number | 0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity pressure | 3.9157 mmWC |
| Sum of coefficients | 3.8000 |
| Fitting losses | 14.880 mmWC |
Open this example in the calculator and change any input.
Formula
\(\Delta p = \left(\sum n_i C_i\right)\frac{\rho v^2}{2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(v\) | Air velocity | m/s |
| \(\rho\) | Air density | kg/m³ |
| \(C_{1}\) | Fitting 1: loss coefficient | - |
| \(n_{1}\) | Fitting 1: number | - |
| \(C_{2}\) | Fitting 2: loss coefficient | - |
| \(n_{2}\) | Fitting 2: number | - |
| \(C_{3}\) | Fitting 3: loss coefficient | - |
| \(n_{3}\) | Fitting 3: number | - |
| \(C_{4}\) | Fitting 4: loss coefficient | - |
| \(n_{4}\) | Fitting 4: number | - |
| \(C_{5}\) | Fitting 5: loss coefficient | - |
| \(n_{5}\) | Fitting 5: number | - |
| \(C_{6}\) | Fitting 6: loss coefficient | - |
| \(n_{6}\) | Fitting 6: number | - |
| \(p_v\) | Velocity pressure | Pa |
| \(\Sigma nC\) | Sum of coefficients | - |
| \(\Delta p\) | Fitting losses | Pa |
Method and standards
Loss coefficient method.
Where it is used
- Fan selection.
- Checking duct systems.
Common mistakes
- C referred to the wrong velocity.
- Forgetting the system effect at the fan.
Assumptions and limits
- Fittings far enough apart.
- Numbers of fittings must be whole.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 21 (duct design: dynamic losses Δp = C p_v)
Questions and answers
Four elbows at 0.25, two at 0.6, a damper at 1.0 and two transitions at 0.3, at 8 m/s?
ΣC 3.8: about 146 Pa.
Where are the C values?
ASHRAE fitting database, SMACNA or the maker.
And straight duct?
Add the friction loss from the duct pressure drop calculator.