FireCADCalc

Filter Pressure Drop at a Different Air Flow

Pressure drop of an air filter at a new air flow from a known drop at a reference flow by the power law, with the share of the final (change) pressure drop.

Inputs

Examples: Fine filter at lower flowCoarse filter at higher flow

About 1 for fibrous media in laminar flow, up to 2 for coarse filters; from the maker's curve.

Results

Pressure drop at the new flow10.797mmWC
Share of the final drop42.353%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Fine filter at lower flow. The inputs, in the units selected above:

InputValue
Pressure drop at the reference flow12.237 mmWC
Reference flow3,400.0 m³/h
New flow3,000.0 m³/h
Flow exponent1.0000 -
Final (change) pressure drop25.493 mmWC

Applying the formula below gives:

ResultValue
Pressure drop at the new flow10.797 mmWC
Share of the final drop42.353 %

Open this example in the calculator and change any input.

Formula

\(\Delta p_2 = \Delta p_1\left(\frac{\dot V_2}{\dot V_1}\right)^n\)

Variables

Symbol Meaning SI unit
\(\Delta p_1\) Pressure drop at the reference flow Pa
\(\dot V_1\) Reference flow m³/s
\(\dot V_2\) New flow m³/s
\(n\) Flow exponent -
\(\Delta p_f\) Final (change) pressure drop Pa
\(\Delta p_2\) Pressure drop at the new flow Pa
\(\Delta p_2/\Delta p_f\) Share of the final drop -

Method and standards

Power law.

Where it is used

  • AHU filter monitoring.
  • Fan selection with dirty filters.

Common mistakes

  • Squared law for fine filters.
  • Comparing clean and dirty drops.

Assumptions and limits

  • Same filter loading. A drop above the final (change) value is flagged.

References

  • Power law Δp ∝ V̇ⁿ (n ≈ 1 for laminar flow through fibrous media)

Questions and answers

120 Pa at 3400 m³/h, run at 3000 m³/h?

About 106 Pa with n = 1.

Why n = 1?

Flow through fine fibres is laminar, so drop is proportional to velocity.

When to change filters?

At the final drop the maker or your fan selection allows.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.