Dehumidifier Capacity and Air Flow for a Moisture Load

Dry-air and volume flow a dehumidifier needs to remove a moisture load, from room conditions and supply humidity ratio, with latent capacity.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 10 kg/h at 30 °C, 55 %, supply 8 g/kgStore 2 kg/h at 20 °C, 45 %, desiccant 2 g/kg

Results

Moisture balance ṁ_a(W_r − W_s) = ṁ_w. Latent capacity at 2,501 kJ/kg. Desiccant units reach very low W_s; refrigerant coils are limited by their dew point.

Room humidity ratio14.675g/kg
Dry air flow0.41616kg/s
Air flow at room conditions1,317.0m³/h
Latent capacity (at 2 501 kJ/kg, the psychrometric convention)6.9472kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 kg/h at 30 °C, 55 %, supply 8 g/kg. The inputs, in the units selected above:

InputValue
Moisture load10.000 kg/h
Room temperature30.000 °C
Room relative humidity to hold55.000 %
Supply air humidity ratio8.0000 g/kg
Barometric pressure101.33 kPa

Applying the formula below gives:

ResultValue
Room humidity ratio14.675 g/kg
Dry air flow0.41616 kg/s
Air flow at room conditions1,317.0 m³/h
Latent capacity (at 2 501 kJ/kg, the psychrometric convention)6.9472 kW

Open this example in the calculator and change any input.

Formula

\(\dot m_a = \frac{\dot m_w}{W_r - W_s}, \quad Q_l = \dot m_wh_{fg}\)

Variables

Symbol Meaning SI unit
\(\dot m_w\) Moisture load kg/s
\(t_r\) Room temperature K
\(\varphi_r\) Room relative humidity to hold -
\(W_s\) Supply air humidity ratio kg/kg
\(p\) Barometric pressure Pa
\(W_r\) Room humidity ratio kg/kg
\(\dot m_a\) Dry air flow kg/s
\(\dot V\) Air flow at room conditions m³/s
\(Q_l\) Latent capacity (at 2 501 kJ/kg, the psychrometric convention) W

Method and standards

Moisture balance.

Where it is used

  • Pool halls, stores, packing rooms.
  • Desiccant and coil dehumidifier selection.

Common mistakes

  • Ignoring infiltration moisture.
  • Room RH set below what the supply can achieve.

Assumptions and limits

  • Steady state; well-mixed room.
  • Latent capacity at h_fg = 2 501 kJ/kg, the latent heat at 0 °C used in psychrometric load formulas; the condensation enthalpy at room temperature is about 2 % lower (about 2 430 kJ/kg at 30 °C).

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 1 (moisture balance)

Questions and answers

How do I find the moisture load?

Add people, open water (pool evaporation), wet processes, infiltration and product drying.

Why does supply dryness matter?

The drier the supply, the less air is needed to carry away the same moisture.

What do the defaults represent?

A 10 kg/h moisture load in a warm room held at 55 %, with supply air at 8 g/kg.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.