Dew Point Calculator (from Temperature and RH)

Dew-point temperature of air from dry-bulb temperature and relative humidity, with the vapour pressure, humidity ratio and the margin to condensation on a cold surface.

IAPWS-IF97 (water and steam)Air conditioning and chillers

Inputs

Examples: 30 °C, 70 % RH; chilled-water pipe at 15 °CControl room 24 °C, 50 %; duct at 14 °CMonsoon 33 °C, 85 %; wall at 30 °C

A chilled-water pipe, duct or wall. Condensation forms when the surface is at or below the dew point.

Results

The surface is at or below the dew point: water will condense on it. Insulate with a vapour barrier or raise the surface temperature.

Dew-point temperature23.928°C
Dew-point depression (air minus dew point)6.0724K
Surface minus dew point (negative = condensation)-8.9276K
Partial pressure of water vapour2.9727kPa
Humidity ratio18.798g/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 °C, 70 % RH; chilled-water pipe at 15 °C. The inputs, in the units selected above:

InputValue
Air temperature (dry bulb)30.000 °C
Relative humidity70.000 %
Barometric pressure (absolute)101.33 kPa
Surface temperature to check15.000 °C

Applying the formula below gives:

ResultValue
Dew-point temperature23.928 °C
Dew-point depression (air minus dew point)6.0724 K
Surface minus dew point (negative = condensation)-8.9276 K
Partial pressure of water vapour2.9727 kPa
Humidity ratio18.798 g/kg

Open this example in the calculator and change any input.

Formula

\(p_v = \varphi\,p_{sat}(T) \qquad T_{dp} = T_{sat}(p_v) \qquad W = \frac{M_w}{M_{da}}\,\frac{p_v}{p - p_v}\)

Variables

Symbol Meaning SI unit
\(T\) air temperature K
\(\varphi\) relative humidity –
\(p\) barometric pressure Pa
\(T_s\) surface temperature to check K
\(T_{dp}\) dew point K
\(T - T_{dp}\) dew-point depression K
\(T_s - T_{dp}\) surface margin (negative = condensation) K
\(p_v\) vapour pressure Pa
\(W\) humidity ratio kg/kg
\(p_{sat}, T_{sat}\) IF97 saturation pressure and temperature Pa, K

Method and standards

The vapour pressure is the relative humidity times the IAPWS-IF97 saturation pressure; the dew point is the IF97 saturation temperature at that vapour pressure.

Where it is used

  • Insulation of chilled-water and cold lines.
  • Switchgear and panel condensation checks.
  • Compressed air and instrument air quality.

Common mistakes

  • Confusing pressure dew point of compressed air with atmospheric dew point.
  • Reading RH near a heat source.
  • Forgetting the vapour barrier on cold insulation.

Assumptions and limits

  • Over liquid water, 0–100 °C; dew points below 0 °C (frost points) are not covered.

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
  • IAPWS-IF97 saturation pressure

Questions and answers

What is the dew point of air at 30 °C and 70 % RH?

23.9 °C. A chilled-water pipe at 15 °C is 8.9 K below it and will sweat unless insulated with a vapour barrier.

Is dew point the same as wet bulb?

No. Dew point is where the air saturates when cooled at constant moisture; wet bulb is where it saturates by evaporating water into it. Wet bulb lies between dew point and dry bulb.

Why use IF97 instead of the Magnus formula?

IF97 is the international standard for water; Magnus is a fit that drifts by a few tenths of a degree.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.