Worked example
Example: Natural gas flue gas, 17.5 % H2O, 1 atm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water vapour content from | Value entered |
| Water vapour in wet flue gas, by volume | 17.500 % |
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Flue gas pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water dew point | 57.480 °C |
| Partial pressure of water vapour | 0.17732 bar |
| Water vapour in wet flue gas used | 17.500 % |
Open this example in the calculator and change any input.
Formula
\(p_{H_2O} = y_{H_2O}\,p \qquad T_{dp} = T_{sat}\!\left(p_{H_2O}\right)\)
When the content comes from the fuel, \(y_{H_2O}\) is the water vapour (from hydrogen, fuel moisture and air humidity) divided by the total wet flue gas, both in kmol per kg of fuel.
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{basis}\) | water vapour content entered, or from the fuel | – |
| \(y_{H_2O}\) | water vapour in wet flue gas by volume, entered | – |
| \(C\), \(H\), \(O\), \(N\), \(S\) | carbon, hydrogen, oxygen, nitrogen, sulphur in the fuel as fired | – |
| \(A\) | ash | – |
| \(M\) | moisture | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(p\) | flue gas absolute pressure | Pa |
| \(T_{dp}\) | water dew point | K |
| \(p_{H_2O}\) | partial pressure of water vapour | Pa |
| \(y\) | water vapour fraction used | – |
Method and standards
Dalton's law of partial pressures for an ideal-gas mixture, and the saturation temperature at the partial pressure from the IAPWS-IF97 region 4 equation (FireCAD's own implementation). The water content from the fuel uses the exact-ratio combustion balance with ASME PTC 4-2013 air.
Where it is used
- Setting the condensing limit for economisers.
- Designing condensing economisers.
- Plume and corrosion studies.
Common mistakes
- Confusing water dew point with acid dew point.
- Using dry gas composition.
- Ignoring air humidity and fuel moisture.
Assumptions and limits
- Ideal-gas mixture; the enhancement factor (below 0.5 % at atmospheric pressure) is neglected; above about 5 bar a warning appears.
- A partial pressure below the triple point (dew point below 0 °C) is rejected; the frost point applies there.
- Pure water: dissolved acids raise the actual condensation temperature (see the acid dew point).
- Complete combustion; no water from atomising steam or soot blowing unless included in the content entered.
References
- IAPWS R7-97(2012) IF97 (saturation)
- ASME PTC 4-2013 (air composition)
Questions and answers
What is the water dew point of natural gas flue gas?
Natural gas flue gas holds about 17–18 % water vapour by volume. At 17.5 % and atmospheric pressure the partial pressure is 17.7 kPa and the dew point 57.5 °C; a condensing economiser must cool the gas below this.
Is the water dew point the same as the acid dew point?
No. Sulphuric acid condenses well above the water dew point, often at 110–150 °C for sulphur-bearing fuels. Use the acid dew point calculator for the cold-end metal temperature.
Why is bagasse flue gas dew point so high?
Bagasse is about half water. With 30 % excess air the flue gas holds 26.7 % water vapour, which gives a dew point of 66.8 °C.