FireCADCalc

Atomising Steam Consumption and Heat Loss

Steam used by steam-atomised oil burners from the oil flow and steam-to-oil ratio, with the heat it carries up the stack as a share of the fuel heat.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalPulp and paperIAPWS-IF97 (water and steam)BoilerFuel oil and gas systemBurner and furnace

Inputs

Examples: 1 t/h oil, 0.3 kg/kg, 8 bar(a), feed 105 °C3 t/h, 0.15, 10 bar(a), 105 °C0.5 t/h, 0.4, 7 bar(a), 80 °C

From the burner maker's data sheet for your burner and load.

Results

Atomising steam300.00kg/h
Heat in the atomising steam193.97kW
Heat lost with it, share of fuel heat1.6239%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 t/h oil, 0.3 kg/kg, 8 bar(a), feed 105 °C. The inputs, in the units selected above:

InputValue
Oil firing rate1,000.0 kg/h
Atomising steam per kg of oil0.30000 kg/kg
Atomising steam pressure (absolute, saturated)8.0000 bar
Feedwater temperature (to value the steam)105.00 °C
Gross calorific value of the oil43,000 kJ/kg

Applying the formula below gives:

ResultValue
Atomising steam300.00 kg/h
Heat in the atomising steam193.97 kW
Heat lost with it, share of fuel heat1.6239 %

Open this example in the calculator and change any input.

Formula

\(\dot m_s = r\,\dot m_o \qquad \dot Q = \dot m_s\,(h_g - h_{fw}) \qquad L = \frac{\dot Q}{\dot m_o \cdot GCV}\)

Variables

Symbol Meaning SI unit
\(\dot m_o\) oil firing rate kg/s
\(r\) atomising steam per kg of oil kg/kg
\(p_s\) atomising steam pressure, absolute Pa
\(T_{fw}\) feedwater temperature K
\(GCV\) gross calorific value of the oil J/kg
\(\dot m_s\) atomising steam kg/s
\(\dot Q\) heat in the atomising steam W
\(L\) loss as a share of fuel heat –
\(h_g\) saturated steam enthalpy (IF97) J/kg
\(h_{fw}\) feedwater enthalpy (IF97) J/kg

Method and standards

Steam valued at the heat added from feedwater to saturated steam, with FireCAD's IAPWS-IF97; all of it is taken as lost with the flue gas. This is a simple upper estimate: strictly the stack carries the vapour at stack temperature and its low partial pressure, which differs from \(h_g\) by a few per cent. Feedwater enthalpy is taken at the atomising pressure, or just above its own saturation pressure when the feedwater is hotter than steam boils at that pressure.

Where it is used

  • Boiler house steam and water balances.
  • Comparing burner atomising methods.
  • Checking burner settings against the maker's data.

Common mistakes

  • Running atomising steam at a fixed high pressure at all loads.
  • Using wet steam, which causes poor atomisation and flame instability.
  • Forgetting the make-up water the steam consumes.

Assumptions and limits

  • Saturated atomising steam; ratio from the burner maker.

References

  • IAPWS R7-97(2012) IF97
  • first law of thermodynamics

Questions and answers

How much steam does a steam-atomised burner use?

The oil flow times the maker's steam-to-oil ratio. 1 t/h of oil at 0.3 kg/kg uses 300 kg/h of steam; raised from 105 °C feedwater at 8 bar(a) it carries 194 kW, 1.6 % of the fuel heat, up the stack.

Can I reduce it?

Set the atomising steam pressure to the maker's curve, not higher; consider air atomising or pressure-jet burners where the oil and turndown allow.

Does it affect efficiency?

Yes, the steam leaves with the flue gas as vapour: the boiler loses its heat and the moisture loss rises.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators