Worked example
Example: Ganapathy: 1,000 lb/h, SG 0.91, 168 °F. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fuel oil flow | 453.59 kg/h |
| Specific gravity at 60/60 °F | 0.91000 - |
| Oil temperature | 75.556 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| API gravity | 23.995 |
| Expansion factor per °F (× 1.8 for per K) | 4.0000e-04 |
| Density at 60 °F | 909.09 kg/m³ |
| Density at temperature | 871.44 kg/m³ |
| Volume flow at 60 °F | 498.95 L/h |
| Volume flow at temperature | 520.51 L/h |
Open this example in the calculator and change any input.
Formula
\(v_t = v_{60}[1 + E(t - 60)]\ (t\ \text{in °F}), \quad °API = \frac{141.5}{SG} - 131.5, \quad \rho_{60} = 999.0\,SG, \quad \rho_t = \frac{\rho_{60}}{1 + E(t - 60)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W\) | Fuel oil flow | kg/s |
| \(SG\) | Specific gravity at 60/60 °F | - |
| \(t\) | Oil temperature | K |
| \(°API\) | API gravity | - |
| \(E\) | Expansion factor per °F (multiply by 1.8 for per K) | 1/°F |
| \(\rho_{60}\) | Density at 60 °F | kg/m³ |
| \(\rho_t\) | Density at temperature | kg/m³ |
| \(\dot V_{60}\) | Volume flow at 60 °F | m³/s |
| \(\dot V_t\) | Volume flow at temperature | m³/s |
Method and standards
Ganapathy's Eq. (23) with the expansion factor chosen by °API band from his Table 3.8 (not reproduced here). Water at 60 °F is taken as 999.0 kg/m³. The volume correction tables of ASTM D1250 / API MPMS 11.1 are not used.
Where it is used
- Fuel oil pump and meter sizing.
- Day-tank stock correction.
Common mistakes
- Applying a water expansion coefficient.
- Mixing °F and °C.
Assumptions and limits
- Linear expansion with temperature and a constant factor per °API band, so the result steps slightly at the band edges.
- Outside the table's °API bands (below 0 or above 94 °API) the end-band factor is used and a note appears.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q3.21
- Eq. (23) and Table 3.8 (expansion factors for fuel oils)
Questions and answers
Why does volume change?
Fuel oil expands about 0.04 % per °F; heated to 168 °F it takes about 4 % more volume.
What does Ganapathy's example give?
1,000 lb/h of SG 0.91 oil: 2.2 gpm at 60 °F and 2.29 gpm at 168 °F.
Is E per °F?
Yes, as tabulated; the calculator converts temperatures.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.