Oil Burner Nozzle Flow and Turndown (Square-Root Law)

Oil flow of a pressure-atomising nozzle at minimum and maximum pressure from its rated flow and pressure (square-root law), and the turndown ratio.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolFuel oil and gas systemBurner and furnace

Inputs

Examples: 300 kg/h at 20 barSmall nozzle

Results

Flow at minimum pressure177.48kg/h
Flow at maximum pressure335.41kg/h
Turndown ratio1.8898

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 300 kg/h at 20 bar. The inputs, in the units selected above:

InputValue
Rated flow300.00 kg/h
Rated pressure drop20.000 bar
Minimum pressure drop7.0000 bar
Maximum pressure drop25.000 bar

Applying the formula below gives:

ResultValue
Flow at minimum pressure177.48 kg/h
Flow at maximum pressure335.41 kg/h
Turndown ratio1.8898

Open this example in the calculator and change any input.

Formula

\(\dot m = \dot m_1\sqrt{\Delta p/\Delta p_1}, \quad TD = \sqrt{\Delta p_{max}/\Delta p_{min}}\)

Variables

Symbol Meaning SI unit
\(\dot m_1\) Rated flow kg/s
\(\Delta p_1\) Rated pressure drop Pa
\(\Delta p_{min}\) Minimum pressure drop Pa
\(\Delta p_{max}\) Maximum pressure drop Pa
\(\dot m_{min}\) Flow at minimum pressure kg/s
\(\dot m_{max}\) Flow at maximum pressure kg/s
\(TD\) Turndown ratio -

Method and standards

Square-root law of an orifice with a constant discharge coefficient, scaled from the nozzle's rated flow and pressure. A note appears when the turndown is above about 2:1.

Where it is used

  • Burner selection.
  • Load range checks.

Common mistakes

  • Supply pressure used instead of nozzle drop.

Assumptions and limits

  • Constant viscosity and discharge coefficient. The flow number of swirl pressure-jet nozzles changes somewhat with pressure and viscosity; use the maker's capacity table where you have it.
  • The minimum pressure for good atomisation is not checked: take it from the nozzle maker.

References

  • Orifice square-root law ṁ ∝ √Δp (constant discharge coefficient)

Questions and answers

Why only √ of the pressure?

Flow through an orifice rises with the square root of the pressure drop.

Why is turndown small?

Doubling the flow needs four times the pressure.

Viscosity?

Heat the oil to the viscosity the nozzle needs; flow at a pressure depends on it.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.