FireCADCalc

EPA Method 19 F-Factors from the Ultimate Analysis

Dry (Fd), wet (Fw) and carbon (Fc) F-factors of a fuel from its ultimate analysis and gross calorific value by US EPA Method 19 (volumes at 20 °C, 1 atm).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolStack and chimney

Inputs

Examples: Biomass analysis: C 45 %, H 3.5 %, moisture 10 %Bituminous coal

Results

Method 19 standard conditions are 20 °C and 760 mm Hg; convert before mixing with 0 °C normal volumes.

Dry F-factor (dscm per GJ)293.22
Wet F-factor (wscm per GJ)325.66
Carbon F-factor (scm CO₂ per GJ)52.941

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Biomass analysis: C 45 %, H 3.5 %, moisture 10 %. The inputs, in the units selected above:

InputValue
Carbon %45.000 %
Hydrogen % (excluding moisture)3.5000 %
Sulphur %0.50000 %
Nitrogen %1.0000 %
Oxygen % (excluding moisture)5.0000 %
Moisture %10.000 %
Gross calorific value (same basis)17,000 kJ/kg

Applying the formula below gives:

ResultValue
Dry F-factor (dscm per GJ)293.22
Wet F-factor (wscm per GJ)325.66
Carbon F-factor (scm CO₂ per GJ)52.941

Open this example in the calculator and change any input.

Formula

\(F_d = K\frac{22.7 H + 9.57 C + 3.54 S + 0.86 N - 2.85 O}{GCV}, \quad F_w = K\frac{34.74 H + 9.57 C + 3.54 S + 0.86 N - 2.85 O + 1.30\,H_2O}{GCV}, \quad F_c = K\frac{2.0 C}{GCV}\)

Variables

Symbol Meaning SI unit
\(C\) Carbon % -
\(H\) Hydrogen % (excluding moisture) -
\(S\) Sulphur % -
\(N\) Nitrogen % -
\(O\) Oxygen % (excluding moisture) -
\(H_2O\) Moisture % -
\(GCV\) Gross calorific value (same basis) J/kg
\(F_d\) Dry F-factor (dscm per GJ) -
\(F_w\) Wet F-factor (wscm per GJ) -
\(F_c\) Carbon F-factor (scm CO₂ per GJ) -
\(K\) 10⁻⁵ (kJ/J)/%, so that with GCV in kJ/kg the F-factor is in m³/J; shown ×10⁹ per GJ -

Method and standards

US EPA Method 19 (40 CFR Part 60 Appendix A-7), Eqs. 19-13 to 19-15 in metric form, at 20 °C and 760 mm Hg. The outputs are in m³ per GJ in every unit system; for dscf/MMBtu divide by 0.02684.

Where it is used

  • Emission reporting in g/GJ.
  • Checking CEMS data.

Common mistakes

  • Moisture's hydrogen and oxygen counted in H and O.

Assumptions and limits

  • Analysis and GCV on the same basis; hydrogen and oxygen exclude the moisture. The calculator cannot check the basis.
  • The analysis must total no more than 100 %, contain some carbon or hydrogen, and give positive F-factors.

References

  • US EPA 40 CFR Part 60 Appendix A-7
  • Method 19
  • Eqs. 19-13 to 19-15 (metric constants Khd 22.7, Kc 9.57, Ks 3.54, Kn 0.86, Ko 2.85, Khw 34.74, Kw 1.30, Kcc 2.0; K = 10⁻⁵)

Questions and answers

What is an F-factor?

The volume of flue gas made per unit of heat in the fuel at stoichiometric combustion.

Why is it handy?

With an F-factor, a stack concentration and O₂ give the emission per unit of heat input, without measuring gas flow.

Typical Fd?

EPA Method 19 Table 19-2 lists about 263 dscm/GJ for bituminous coal and about 248 for wood.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.