Worked example
Example: 5 MW burner, NG 34 MJ/Nm³, 2 bar(a), 20 °C, 80 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Burner heat input (on NCV) | 5,000.0 kW |
| Net calorific value of the gas, per Nm³ | 34.000 MJ/Nm³ |
| Gas pressure in the line | 0.98675 bar g |
| Gas temperature | 20.000 °C |
| Pipe inside diameter | 80.000 mm |
| Compressibility factor | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gas flow at normal conditions (0 °C, 1.01325 bar) | 529.41 Nm³/h |
| Actual gas flow in the line | 287.85 m³/h |
| Velocity in the pipe | 15.907 m/s |
Open this example in the calculator and change any input.
Formula
\(\dot V_n = \frac{\dot Q}{NCV} \qquad \dot V = \dot V_n\,\frac{p_n}{p}\,\frac{T}{T_n}\,Z \qquad v = \frac{\dot V}{\pi D^2/4}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | burner heat input on NCV | W |
| \(NCV\) | net calorific value per Nm³ | J/m³ |
| \(p\) | line pressure (absolute in SI; shown and entered as gauge) | Pa |
| \(T\) | gas temperature | K |
| \(D\) | pipe inside diameter | m |
| \(Z\) | compressibility factor | – |
| \(\dot V_n\) | flow at normal conditions | Nm³/s |
| \(\dot V\) | actual flow | m³/s |
| \(v\) | velocity in the pipe | m/s |
| \(p_n\), \(T_n\) | normal pressure and temperature, 101 325 Pa and 273.15 K | Pa, K |
Method and standards
Ideal-gas conversion between normal and line conditions with a compressibility factor.
Where it is used
- Sizing gas trains, regulators and meters.
- Checking burner gas consumption against the meter.
- Gas supply contracts and budgets.
Common mistakes
- Using GCV with an efficiency on NCV, or the reverse.
- Treating gauge pressure as absolute.
- Mixing normal and standard cubic metres.
Assumptions and limits
- Single gas composition; compressibility at line conditions as entered (1 is fine at low pressure); at normal conditions Z is taken as 1 (about 0.998 for natural gas, a 0.2 % difference).
- Normal volumes are at 0 °C and 101.325 kPa, and the NCV per Nm³ is on that same basis; scfm and Btu/scf are converted to the US standard cubic foot (60 °F, 14.696 psia).
- The 20 m/s velocity warning is a common design limit, not a code value.
References
- Ideal-gas law with compressibility; normal conditions 0 °C and 101.325 kPa
Questions and answers
How much gas does a 5 MW burner use?
Heat input over NCV: 5 MW at 34 MJ/Nm³ is 529 Nm³/h. At 2 bar(a) and 20 °C that is 288 m³/h actual, 15.9 m/s in an 80 mm pipe.
Why convert to actual m³/h?
Pipes, valves and meters see the actual volume at line pressure. Sizing on Nm³/h overstates the volume of pressurised gas.
Normal or standard cubic metres?
Normal is 0 °C and 101.325 kPa; "standard" conditions vary (15 °C or 20 °C). Check which one your gas bill and calorific value use.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.