Worked example
Example: Ganapathy: natural gas 4 psig to propane. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Burner pressure with the old gas | 27.579 kPa |
| Old gas heating value (per standard volume, same reference as the new gas) | 41.429 MJ/Nm³ |
| Old gas specific gravity (air = 1) | 0.60000 - |
| New gas heating value | 90.750 MJ/Nm³ |
| New gas specific gravity | 1.5000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Burner pressure with the new gas | 14.370 kPa |
| Volume flow ratio, new/old | 0.45652 |
| Wobbe index ratio | 1.3854 |
Open this example in the calculator and change any input.
Formula
\(\frac{\Delta p_2}{\Delta p_1} = \frac{S_2}{S_1}\left(\frac{HHV_1}{HHV_2}\right)^2, \quad WI = \frac{HHV}{\sqrt{S}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p_1\) | Burner pressure with the old gas | Pa |
| \(HHV_1\) | Old gas heating value (per standard volume) | J/m³ |
| \(S_1\) | Old gas specific gravity (air = 1) | - |
| \(HHV_2\) | New gas heating value | J/m³ |
| \(S_2\) | New gas specific gravity | - |
| \(\Delta p_2\) | Burner pressure with the new gas | Pa |
| \(\dot V_2/\dot V_1\) | Volume flow ratio, new/old | - |
| \(WI_2/WI_1\) | Wobbe index ratio | - |
Method and standards
Mass flow = Q/HHV × ρ_std; Δp = K W²/ρ with ρ ∝ S. Only the ratios matter, so both heating values must be on the same basis (both gross, per the same standard volume); the default values are Ganapathy's 1050 and 2300 Btu/scf (60 °F, 14.696 psia) converted to normal m³ at 0 °C.
Where it is used
- Fuel switching on gas burners.
- Standby LPG systems.
Common mistakes
- Ignoring the back pressure in the furnace.
- Mixing gross and net heating values.
Assumptions and limits
- Same burner and back pressure; same gas temperature. The burner pressure is the drop across the burner: with a pressurised furnace, or a fixed regulator or valve drop upstream, subtract those from the supply pressure first.
- Incompressible flow; above about 0.5 bar a note appears.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q2.05
- Eq. (7): Δp = K W²/ρ
Questions and answers
Why does propane need lower pressure?
It carries more than twice the heat per standard cubic metre, so far less volume flows for the same duty.
What does Ganapathy's example give?
Natural gas at 4 psig switched to propane (2300 Btu/scf, SG 1.5) needs about 2.1 psig.