Worked example
Example: Ganapathy ch. 3 Ex. 8: 119,275 lb/h air, 14,000 lb/h FGR, 23 % O2 by mass (book 18.75 % O2). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Combustion air flow (dry) | 54,102 kg/h |
| Recirculated flue gas flow | 6,350.3 kg/h |
| Oxygen in air, by mass | 23.000 % |
| Flue gas CO₂, % vol (wet) | 8.2900 - |
| Flue gas H₂O, % vol (wet) | 18.170 - |
| Flue gas N₂, % vol (wet) | 71.070 - |
| Flue gas O₂, % vol (wet) | 2.4700 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Recirculation ratio (mass) | 11.738 % |
| Windbox O₂, % vol wet | 18.735 |
| Windbox O₂, % vol dry | 19.115 |
| Windbox CO₂, % vol | 0.90505 |
| Windbox H₂O, % vol | 1.9837 |
Open this example in the calculator and change any input.
Formula
\(\dot n_i = \frac{W_rw_{i,fg}}{M_i} + \frac{W_aw_{i,air}}{M_i}, \quad y_i = \frac{\dot n_i}{\sum\dot n}, \quad w_{i,fg} = \frac{y_{i,fg}M_i}{\bar M_{fg}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W_a\) | Combustion air flow (dry) | kg/s |
| \(W_r\) | Recirculated flue gas flow | kg/s |
| \(w_{O_2,air}\) | Oxygen in air, by mass | - |
| \(CO_2\) | Flue gas CO₂, % vol (wet) | - |
| \(H_2O\) | Flue gas H₂O, % vol (wet) | - |
| \(N_2\) | Flue gas N₂, % vol (wet) | - |
| \(O_2\) | Flue gas O₂, % vol (wet) | - |
| \(W_r/W_a\) | Recirculation ratio (mass) | - |
| \(O_{2,wb}\) | Windbox O₂, % vol wet | - |
| \(O_{2,wb,dry}\) | Windbox O₂, % vol dry | - |
| \(CO_{2,wb}\) | Windbox CO₂, % vol | - |
| \(H_2O_{wb}\) | Windbox H₂O, % vol | - |
Method and standards
Mass and mole balance of the air and recirculated gas, with the molar masses Ganapathy's example uses (CO₂ 44.01, H₂O 18.015, N₂ 28.013, O₂ 31.999). The flue gas analysis is wet and normalised to 100 %.
Where it is used
- Low-NOx packaged boilers with FGR.
- Checking windbox O₂ analyser readings.
Common mistakes
- Using dry flue gas analysis for wet recirculated gas.
- Too much FGR causing flame instability.
Assumptions and limits
- Dry air; argon with nitrogen.
- The flue gas analysis must be wet (a dry analysis leaves out the water); an analysis not adding to 100 % is normalised with a note.
References
- Ganapathy
- Industrial Boilers and Heat Recovery Steam Generators (Marcel Dekker, 2003)
- ch. 3
- Example 8 (oxygen in the windbox with flue gas recirculation)
Questions and answers
Why recirculate flue gas?
Inert gas in the combustion air lowers the flame temperature and so thermal NOx; 15–25 % FGR typically halves NOx on gas firing.
What does Ganapathy's example give?
119,275 lb/h of air with 14,000 lb/h of gas at 2.47 % O₂: windbox O₂ 18.75 %, CO₂ 0.9 %, H₂O 2.0 %.
Does FGR cost efficiency?
A little: fan power rises and more gas passes through the boiler, but exit gas loss changes only slightly because the recirculated gas returns its heat.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.