Worked example
Example: Indian coal, 25 % excess air, 300 ppm CO. The inputs, in the units selected above:
| Input | Value |
|---|---|
| CO in dry flue gas | 300.00 ppm |
| Carbon | 45.000 % |
| Hydrogen | 3.5000 % |
| Oxygen | 5.0000 % |
| Nitrogen | 1.0000 % |
| Sulphur | 0.50000 % |
| Ash | 35.000 % |
| Moisture | 10.000 % |
| Excess air | 25.000 % |
| Air humidity (kg water per kg dry air) | 0.013000 kg/kg |
| Gross calorific value of the fuel, as fired | 18,600 kJ/kg |
| Fuel firing rate | 12,000 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| CO loss, % of heat input | 0.27778 % |
| Heat lost as CO | 172.22 kW |
| CO per kg of fuel | 2.1863 g/kg |
| CO concentration, dry, normal | 374.90 mg/Nm³ |
Open this example in the calculator and change any input.
Formula
\(m_{CO} = CO_{dry}\cdot n_{dg}\cdot M_{CO} \qquad L_{CO} = \frac{m_{CO}\cdot HHV_{CO}}{GCV} \qquad \dot Q_{CO} = \dot m_f\,m_{CO}\,HHV_{CO}\)
\(c_{CO} = \frac{CO_{dry}\,M_{CO}}{V_m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(CO_{dry}\) | CO in dry flue gas, volume fraction | – |
| \(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) | ultimate analysis as fired, mass fractions | – |
| \(EA\) | excess air | – |
| \(\omega\) | air humidity, kg water per kg dry air | kg/kg |
| \(GCV\) | gross calorific value | J/kg |
| \(\dot m_f\) | fuel firing rate | kg/s |
| \(L_{CO}\) | CO loss, fraction of input | – |
| \(\dot Q_{CO}\) | heat lost as CO | W |
| \(m_{CO}\) | CO per kg of fuel | kg/kg |
| \(c_{CO}\) | CO concentration, dry, at 0 °C and 101.325 kPa | kg/m³ |
| \(n_{dg}\) | dry flue gas per kg of fuel, from the combustion balance | kmol/kg |
| \(M_{CO}\) | molar mass of CO, 28.010 kg/kmol | kg/kmol |
| \(HHV_{CO}\) | heat of burning CO to CO₂, 10 160 Btu/lb = 23.63 MJ/kg (PTC 4) | J/kg |
| \(V_m\) | molar volume at normal conditions, 22.414 m³/kmol | m³/kmol |
Method and standards
CO loss as in ASME PTC 4 §5.14: the mass of CO per kg of fuel times the heat of burning CO to CO₂, 10 160 Btu/lb, over the gross calorific value. The dry flue gas quantity comes from FireCAD's exact-ratio combustion balance of the fuel analysis at the given excess air.
Where it is used
- Efficiency tests and combustion tuning of coal, oil, gas and biomass boilers and furnaces.
- Setting the O₂ trim floor: the lowest O₂ before CO rises sharply.
- Converting the analyser's ppm to mg/Nm³ for emission reports.
Common mistakes
- Using a wet-basis CO reading with the dry gas quantity, or the reverse.
- Reading CO at one point in a large duct: CO stratifies, so traverse the duct.
- Looking only at the CO loss when lowering excess air, without the dry gas saving on the other side.
- Forgetting that hydrogen and soot may also be unburned when CO is high.
Assumptions and limits
- CO is the only unburned gas; hydrogen and hydrocarbons are not counted.
- The gas quantity is computed with all carbon burned to CO₂ (the CO share is small). Above about 1 % CO the dry gas is noticeably understated and a warning appears.
- Excess air must be the value at the CO sampling point, consistent with the O₂ the analyser reads there; use the excess air from O₂ calculator.
- Air humidity changes only the wet flue gas; the dry gas quantity, and so every output here, does not depend on it.
- A warning appears when the GCV differs from the Channiwala–Parikh estimate of the analysis by more than 15 %.
References
- ASME PTC 4-2013 Fired Steam Generators §5.14 (CO loss)
- BIS IS 8753 (boiler efficiency)
Questions and answers
How much efficiency does CO cost?
Less than most people think at normal readings. Coal at 25 % excess air with 300 ppm CO in dry flue gas loses 2.2 g of CO per kg of fuel, 0.28 % of the heat input. At 2000 ppm it is nearly 2 % and a sign of a combustion problem.
Why does the loss depend on the fuel and excess air?
The analyser gives a concentration; the loss needs the mass of CO per kg of fuel, which is that concentration times the dry flue gas per kg of fuel. More excess air means more gas, so the same ppm costs more.
What is 300 ppm in mg/Nm³?
About 375 mg/Nm³ dry, at 0 °C and 1.01325 bar. Emission limits are usually set at a reference O₂; correct the value with the O₂ correction calculator.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.