Combustion of Solid and Liquid Fuels

Air required, flue gas produced and its composition, and calorific values of coal, biomass or oil from the ultimate analysis and excess air.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalThermic fluid heatingPulp and paperASME PTC 4 (fired steam generators)BoilerBurner and furnaceBoiler attendant and boiler operator examinations

This calculator is a step of the workflow Boiler: fuel to fans: enter the data once and each step feeds the next.

Inputs

Examples: Fuel oil No. 6, GCV entered 42.5 MJ/kgBituminous coalIndian coal, 35 % ashBagasse, 50 % moistureWood chips, 30 % moisture

Ultimate analysis, as fired, by mass

Leave 0 to estimate by Channiwala–Parikh.

Results

Gross calorific value used18,613kJ/kg
GCV estimate, Channiwala–Parikh18,613kJ/kg
GCV estimate, Dulong (for comparison)19,475kJ/kg
Net calorific value17,605kJ/kg
Stoichiometric oxygen1.4316kg/kg
Theoretical dry air6.1858kg/kg
Actual dry air7.4230kg/kg
Actual wet air7.5195kg/kg
Wet flue gas8.1695kg/kg
Dry flue gas7.6602kg/kg
Water vapour in flue gas0.50926kg/kg
Wet flue gas volume (normal)6.2260Nm³/kg
CO₂ in wet flue gas13.525%
H₂O in wet flue gas10.177%
N₂ in wet flue gas72.163%
Ar in wet flue gas0.85799%
O₂ in wet flue gas3.2213%
SO₂ in wet flue gas0.056146%
O₂ in dry flue gas (analyser reading)3.5863%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Fuel oil No. 6, GCV entered 42.5 MJ/kg. The inputs, in the units selected above:

InputValue
Carbon85.500 %
Hydrogen11.500 %
Oxygen0.70000 %
Nitrogen0.20000 %
Sulphur2.0000 %
Ash0.10000 %
Moisture0 %
Gross calorific value, as fired (0 = estimate)42,500 kJ/kg
Excess air15.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg

Applying the formula below gives:

ResultValue
Gross calorific value used42,500 kJ/kg
GCV estimate, Channiwala–Parikh43,522 kJ/kg
GCV estimate, Dulong (for comparison)45,682 kJ/kg
Net calorific value39,991 kJ/kg
Stoichiometric oxygen3.2034 kg/kg
Theoretical dry air13.842 kg/kg
Actual dry air15.918 kg/kg
Actual wet air16.125 kg/kg
Wet flue gas17.124 kg/kg
Dry flue gas15.889 kg/kg
Water vapour in flue gas1.2346 kg/kg
Wet flue gas volume (normal)13.221 Nm³/kg
CO₂ in wet flue gas12.106 %
H₂O in wet flue gas11.619 %
N₂ in wet flue gas72.758 %
Ar in wet flue gas0.86646 %
O₂ in wet flue gas2.5459 %
SO₂ in wet flue gas0.10576 %
O₂ in dry flue gas (analyser reading)2.8806 %

Open this example in the calculator and change any input.

Formula

Oxygen demand per kg fuel from the elemental reactions C + O₂ → CO₂, H₂ + ½O₂ → H₂O, S + O₂ → SO₂, less the oxygen in the fuel:

\(m_{O_2} = \frac{M_{O_2}}{M_C}\,C + \frac{M_{O_2}}{2\,M_{H_2}}\,H + \frac{M_{O_2}}{M_S}\,S - O\)

\(m_{a,th} = \frac{m_{O_2}}{w_{O_2}} \qquad m_a = m_{a,th}\,(1 + EA) \qquad m_{a,wet} = m_a\,(1 + \omega)\)

Flue gas per kg fuel:

\(m_{CO_2} = \frac{M_{CO_2}}{M_C}\,C \qquad m_{H_2O} = \frac{M_{H_2O}}{M_{H_2}}\,H + M + \omega\,m_a \qquad m_{SO_2} = \frac{M_{SO_2}}{M_S}\,S \qquad m_{N_2} = N + (1 - w_{O_2})\,m_a \qquad m_{O_2,x} = w_{O_2}\,m_a - m_{O_2}\)

\(m_{g,wet} = m_{CO_2} + m_{H_2O} + m_{SO_2} + m_{N_2} + m_{O_2,x} \qquad m_{g,dry} = m_{g,wet} - m_{H_2O} \qquad y_i = \frac{m_i / M_i}{\sum_j m_j / M_j} \qquad V_g = V_m \sum_j \frac{m_j}{M_j}\)

Heating values:

\(GCV_{CP} = \left(0.3491\,C' + 1.1783\,H' + 0.1005\,S' - 0.1034\,O' - 0.0151\,N' - 0.0211\,A'\right)\,\mathrm{MJ/kg} \times (1 - M) \qquad NCV = GCV - h_{fg,25}\left(\frac{M_{H_2O}}{M_{H_2}}\,H + M\right)\)

\(GCV_D = \left[14\,600\,C + 62\,000\left(H - \frac{O}{8}\right) + 4\,050\,S\right]\ \mathrm{Btu/lb} \qquad GCV = \begin{cases} GCV_{in} & GCV_{in} > 0 \ GCV_{CP} & \text{otherwise} \end{cases}\)

Variables

Symbol Meaning SI unit
\(C\), \(H\), \(O\), \(N\), \(S\), \(A\), \(M\) carbon, hydrogen, oxygen, nitrogen, sulphur, ash, moisture, mass fractions as fired –
\(C'\) … \(A'\) the same on a dry basis, in mass % (Channiwala–Parikh) %
\(GCV_{in}\) gross calorific value entered (0 to estimate) J/kg
\(EA\) excess air fraction –
\(\omega\) humidity of the combustion air, kg water per kg dry air kg/kg
\(GCV\) gross calorific value used J/kg
\(GCV_{CP}\) Channiwala–Parikh estimate J/kg
\(GCV_{D}\) Dulong estimate J/kg
\(NCV\) net calorific value J/kg
\(h_{fg,25}\) latent heat of water at 25 °C, 2 441.7 kJ/kg (IF97) J/kg
\(M_i\) molar masses (IUPAC 2013) kg/kmol
\(w_{O_2}\) oxygen mass fraction of dry air, 0.2314 (20.95 % by volume) –
\(m_{O_2}\) stoichiometric oxygen per kg fuel kg/kg
\(m_{a,th}\), \(m_{a}\), \(m_{a,wet}\) theoretical dry air, actual dry air, actual wet air per kg fuel kg/kg
\(m_{g,wet}\), \(m_{g,dry}\) wet and dry flue gas per kg fuel kg/kg
\(m_{H_2O}\) water vapour in the flue gas per kg fuel kg/kg
\(V_g\) wet flue gas volume per kg fuel at 0 °C and 101.325 kPa Nm³/kg
\(V_m\) molar volume at normal conditions, 22.41397 Nm³/kmol
\(m_{N_2}\) nitrogen, argon and air CO₂ carried through, per kg fuel (the output \(y_{N_2}\) is N₂ alone; argon is shown separately) kg/kg
\(y_{CO_2}\), \(y_{H_2O}\), \(y_{N_2}\), \(y_{Ar}\), \(y_{O_2}\), \(y_{SO_2}\) wet flue gas composition by volume –
\(y_{O_2,dry}\) oxygen in dry flue gas, as an analyser reads it –

Method and standards

Exact molar ratios from IUPAC 2013 atomic masses (32/12.011 for carbon, not 2.667). Air is 20.95 % O₂, 78.08 % N₂, 0.93 % Ar and 0.04 % CO₂ by volume (U.S. Standard Atmosphere, as ASME PTC 4); argon and the air's CO₂ are carried through to the flue gas, so the "nitrogen" of older methods appears here as N₂ plus Ar. The GCV estimate is the Channiwala–Parikh (2002) unified correlation (owner decision 2026-11-09); Dulong is shown for comparison. NCV uses the IF97 latent heat at 25 °C and the exact 8.936 kg of water per kg of hydrogen.

Where it is used

  • Sizing FD and ID fans, ducts and stacks from the air and flue gas quantities.
  • Burner and furnace design for coal, biomass, bagasse and oil.
  • Emission reports: converting analyser readings with the dry and wet gas volumes.
  • The first step of an efficiency calculation by the loss method.

Common mistakes

  • Using the proximate analysis (volatile matter, fixed carbon) where the ultimate analysis (C, H, O, N, S) is needed.
  • Mixing as-received, air-dried and dry bases in one analysis.
  • Forgetting the moisture in the combustion air, which adds water vapour to the gas.
  • Taking the theoretical air as the air the fan must supply: add excess air and leakage.

Assumptions and limits

  • Complete combustion: no CO, no unburned carbon, all sulphur to SO₂. For losses with incomplete combustion use the boiler efficiency calculator.
  • The analysis must sum to 100 % ± 0.5 %.
  • An entered GCV must be on the same as-fired basis as the analysis; a dry-basis laboratory value gives a wrong NCV. A warning appears only when it differs from the Channiwala–Parikh estimate by more than 15 %.
  • Channiwala–Parikh range: C 0–92 %, H 0.43–25 %, O 0–50 %, N 0–5.6 %, ash 0–71 % (dry basis); outside it the estimate is flagged.
  • A net calorific value of zero or below is flagged: such a fuel cannot sustain combustion on its own.

References

  • ASME PTC 4-2013 (air composition, stoichiometry)
  • Channiwala & Parikh (2002) Fuel 81 1051–1063
  • Dulong's formula

Questions and answers

Should the analysis be as fired, dry, or dry ash-free?

As fired, including moisture and ash, so that air and gas come out per kilogram of fuel actually burned. Convert a dry analysis by multiplying each constituent by (1 − moisture).

Why is the O₂ in dry flue gas lower than the excess air suggests?

Because nitrogen dilutes it. 20 % excess air gives only about 3.6 % O₂ in dry gas for coal. Use the flue gas analyser calculator to go the other way.

Which GCV estimate should I trust?

Channiwala–Parikh (2002) was fitted to 225 fuels from biomass to anthracite with an average error of 1.45 %. Dulong is older and less reliable for high-oxygen fuels such as wood and bagasse (here it reads well below Channiwala–Parikh for them); it is shown for comparison. A laboratory value always beats both.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators