Worked example
Example: Control room 600 m³, 2 ACH, 38 °C 45 % outside, 24 °C 50 % inside. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room volume | 600.00 m³ |
| Air changes per hour | 2.0000 - |
| Outdoor dry bulb | 38.000 °C |
| Outdoor relative humidity | 45.000 % |
| Indoor dry bulb | 24.000 °C |
| Indoor relative humidity | 50.000 % |
| Barometric pressure (absolute) | 101.33 kPa |
| Fresh-air flow (0 = use the air changes) | 0 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total load (positive = cooling) | 14.296 kW |
| Sensible load | 5.2581 kW |
| Latent load | 9.0379 kW |
| Outdoor air flow | 1,200.0 m³/h |
| Dry-air mass flow | 1,321.3 kg/h |
Open this example in the calculator and change any input.
Formula
\(\dot V_o = \frac{n\,V_r}{3600}\ \text{or}\ \dot V_f \qquad \dot m_{da} = \frac{\dot V_o}{v_o} \qquad \dot Q_t = \dot m_{da}(h_o - h_i) \qquad \dot Q_s = \dot m_{da}\,[h(T_o, W_i) - h_i] \qquad \dot Q_l = \dot Q_t - \dot Q_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_r\) | room volume | m³ |
| \(n\) | air changes per hour | 1/h |
| \(T_o\) | outdoor dry bulb | K |
| \(\varphi_o\) | outdoor RH | – |
| \(T_i\) | indoor dry bulb | K |
| \(\varphi_i\) | indoor RH | – |
| \(p\) | barometric pressure | Pa |
| \(\dot V_f\) | fresh-air flow at the outdoor state (used instead of n V_r when above 0) | m³/s |
| \(\dot Q_t\) | total load | W |
| \(\dot Q_s\) | sensible load | W |
| \(\dot Q_l\) | latent load | W |
| \(\dot V_o\) | outdoor air flow | m³/s |
| \(\dot m_{da}\) | dry-air flow | kg/s |
| \(h_o, h_i\) | outdoor and indoor enthalpy | J/kg |
| \(W_i\) | indoor humidity ratio | kg/kg |
| \(v_o\) | outdoor specific volume | m³/kg |
Method and standards
Energy balance on the outdoor air brought to room conditions, with ASHRAE moist-air enthalpy.
Where it is used
- Control rooms, MCC and battery rooms.
- Pressurisation air for electrical rooms.
- Fresh-air requirement checks.
Common mistakes
- Using the room volume flow at indoor density for outdoor air.
- Ignoring latent load in humid seasons.
- Leaving out infiltration through doors.
Assumptions and limits
The outdoor air flow is n V_r/3600 from the air changes, or the fresh-air flow entered (at the outdoor state) when that is above zero.
Steady state; the outdoor air is fully brought to room conditions.
References
- ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
Questions and answers
What load do 2 air changes bring into a 600 m³ control room?
With 38 °C 45 % outside and 24 °C 50 % inside: 14.3 kW total, of which 5.3 kW sensible and 9.0 kW latent.
Why is the latent part so large?
Humid outdoor air carries much more moisture than the conditioned room; in monsoon climates latent often exceeds sensible.
Does it work for heating?
Yes: in winter the result is negative, meaning heat must be added.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.