Worked example
Example: ISO 7 at 0.5 µm, four people. The inputs, in the units selected above:
| Input | Value |
|---|---|
| ISO class number | 7.0000 - |
| Particle size considered | 0.50000 µm |
| Particles per person per second (≥ D) | 100,000 - |
| People in the room | 4.0000 - |
| Other generation (particles/s) | 10,000 - |
| Supply air concentration (particles/m³) | 0 - |
| Ventilation effectiveness | 80.000 % |
| Room volume | 300.00 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Class limit (particles/m³) | 351,676 |
| Total generation (particles/s) | 410,000 |
| Supply air flow | 5,246.3 m³/h |
| Air changes per hour | 17.488 |
Open this example in the calculator and change any input.
Formula
\(C_n = 10^N\left(\frac{0.1}{D}\right)^{2.08}, \quad \dot V = \frac{G}{\varepsilon_v(C_n - C_s)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | ISO class number | - |
| \(D\) | Particle size considered | m |
| \(g_p\) | Particles per person per second (≥ D) | - |
| \(n\) | People in the room | - |
| \(G_o\) | Other generation (particles/s) | - |
| \(C_s\) | Supply air concentration (particles/m³) | - |
| \(\varepsilon_v\) | Ventilation effectiveness | - |
| \(V\) | Room volume | m³ |
| \(C_n\) | Class limit (particles/m³) | - |
| \(G\) | Total generation (particles/s) | - |
| \(\dot V\) | Supply air flow | m³/s |
| \(ACH\) | Air changes per hour | - |
Method and standards
Particle balance.
Where it is used
- Pharma, food and electronics clean rooms.
- Control and instrument rooms.
Common mistakes
- Ignoring people generation.
- Designing with no safety factor.
Assumptions and limits
- Non-unidirectional (mixed) flow; steady state.
- No safety factor is applied: the flow holds the room exactly at the class limit. Multiply by your design factor (often 2 or more).
References
- ISO 14644-1 class formula C_n = 10^N(0.1/D)^2.08; steady well-mixed particle balance (ASHRAE Handbook—HVAC Applications (2019), ch. 19)
Questions and answers
Why are people the main source?
A person sheds 10⁵–10⁷ particles per minute depending on garments and activity; gowning cuts this sharply.
Why do real clean rooms use more air?
Designers add safety factors for recovery after doors open, uneven mixing and process upsets.
What do the defaults represent?
An ISO 7 room at 0.5 µm with four gowned people and HEPA-filtered supply.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.