Worked example
Example: 60 W/m² in a 20 °C room, R 0.10. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Required heat output | 0.060000 kW/m² |
| Room temperature | 20.000 °C |
| Thermal resistance above the pipes (screed and covering) | 0.10000 m²·K/W |
| Water temperature drop | 5.0000 K |
| Floor area of the loop | 20.000 m² |
| Floor surface temperature limit | 29.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mean floor surface temperature | 25.656 °C |
| Mean water temperature | 31.656 °C |
| Flow (supply) temperature | 34.156 °C |
| Loop water flow | 206.40 kg/h |
| Output at the floor temperature limit | 0.10001 kW/m² |
Open this example in the calculator and change any input.
Formula
\(q = 8.92(\theta_F - \theta_i)^{1.1}, \quad \theta_w = \theta_F + qR, \quad \dot m = \frac{qA}{c_p\Delta\theta_w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(q\) | Required heat output | W/m² |
| \(\theta_i\) | Room temperature | K |
| \(R\) | Thermal resistance above the pipes (screed and covering) | m²·K/W |
| \(\Delta\theta_w\) | Water temperature drop | K |
| \(A\) | Floor area of the loop | m² |
| \(\theta_F\) | Mean floor surface temperature | K |
| \(\theta_w\) | Mean water temperature | K |
| \(\theta_V\) | Flow (supply) temperature | K |
| \(\dot m\) | Loop water flow | kg/s |
| \(\theta_{F,max}\) | Floor surface temperature limit | K |
| \(q_{max}\) | Output at the floor temperature limit | W/m² |
Method and standards
EN 1264 basic curve.
Where it is used
- Heat pump floor heating.
- Checking floor coverings.
Common mistakes
- Ignoring floor surface limits.
- Thick rugs on heated floors.
Assumptions and limits
The water temperature is a one-dimensional estimate, θ_w = θ_F + qR: EN 1264's full method also uses the pipe spacing, pipe size and the logarithmic water-to-room temperature difference, so the water temperature can be underestimated, more so for wide pipe spacing.
The floor temperature limit defaults to 29 °C (occupied zones); EN 1264 allows higher surface temperatures in bathrooms and perimeter zones: enter the limit that applies.
One-dimensional; uniform floor.
References
- EN 1264-2 basic characteristic curve q = 8.92(θ_F,m − θ_i)^1.1 W/m²; one-dimensional conduction through the floor layers
Questions and answers
How much can a floor give?
At a 29 °C surface in a 20 °C room, about 100 W/m²; more needs perimeter zones at up to 35 °C.
Why do carpets matter?
They add resistance above the pipes, so the water must be hotter for the same output.
What do the defaults represent?
A living room needing 60 W/m² through screed and a thin floor covering.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.