Worked example
Example: Office 300/200/200/60 m², 21 °C in, 5 °C out, 1 500 K·day. The inputs, in the units selected above:
| Input | Value |
|---|---|
| U-value of the walls | 0.60000 W/(m²·K) |
| U-value of the roof | 0.40000 W/(m²·K) |
| U-value of the floor | 0.50000 W/(m²·K) |
| U-value of the windows | 2.8000 W/(m²·K) |
| Area of the walls | 300.00 m² |
| Area of the roof | 200.00 m² |
| Area of the floor | 200.00 m² |
| Area of the windows | 60.000 m² |
| Indoor temperature | 21.000 °C |
| Outdoor design temperature | 5.0000 °C |
| Degree-days for the season (K·day, 0 = none) | 1,500.0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Through the walls | 2.8800 kW |
| Through the roof | 1.2800 kW |
| Through the floor | 1.6000 kW |
| Through the windows | 2.6880 kW |
| Total fabric heat loss (negative = heat gain) | 8.4480 kW |
| Fabric heat loss coefficient | 0.52800 kW/K |
| Seasonal fabric heat loss | 19,008 kWh |
Open this example in the calculator and change any input.
Formula
\(Q_i = U_i A_i (T_i - T_o)\)
\(\Sigma UA = \sum U_i A_i, \quad Q = \Sigma UA\, (T_i - T_o)\)
\(E = \Sigma UA \cdot DD \cdot 86\,400\ \text{s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(U_1\) | U-value of walls | W/(m²·K) |
| \(U_2\) | U-value of roof | W/(m²·K) |
| \(U_3\) | U-value of floor | W/(m²·K) |
| \(U_4\) | U-value of windows | W/(m²·K) |
| \(A_1\) | wall area | m² |
| \(A_2\) | roof area | m² |
| \(A_3\) | floor area | m² |
| \(A_4\) | window area | m² |
| \(U_i\) | U-value of element i | W/(m²·K) |
| \(A_i\) | area of element i | m² |
| \(T_i\) | indoor temperature | K |
| \(T_o\) | outdoor temperature | K |
| \(DD\) | degree-days | K·day |
| \(Q_1\) | through walls | W |
| \(Q_2\) | through roof | W |
| \(Q_3\) | through floor | W |
| \(Q_4\) | through windows | W |
| \(Q_i\) | through element i | W |
| \(Q\) | Total fabric heat loss (negative = heat gain) | W |
| \(\Sigma UA\) | fabric heat loss coefficient | W/K |
| \(E\) | seasonal fabric heat loss | J |
Method and standards
Steady conduction through each element is U A ΔT; the sum gives the fabric load. Seasonal energy uses degree-days, the sum over the season of the daily temperature difference below the base temperature.
Where it is used
- Sizing heating for offices, control rooms and workshops.
- Comparing insulation upgrades.
- Estimating seasonal heating energy.
Common mistakes
- Using centre-of-panel U-values and ignoring thermal bridges.
- Forgetting ventilation and infiltration.
- Using degree-days to a different base temperature.
Assumptions and limits
- Steady state; no solar or internal gains; fabric only.
- When outdoor is warmer than indoor the losses come out negative (gains). The seasonal energy is ΣUA times whatever degree-days you enter: heating degree-days for heating, cooling degree-days for cooling.
References
- Steady-state conduction Q = U A ΔT
- Degree-day method
Questions and answers
What is the fabric loss of the example office?
8.4 kW at 16 K difference: UA 528 W/K across walls, roof, floor and windows; 1 500 degree-days give about 19 000 kWh a season.
Why are windows so important?
Their U-value is several times a wall's; in the example 60 m² of glass loses nearly as much as 300 m² of wall.
Does this work for cooling?
Yes for conduction: a negative result is a heat gain. Add solar and internal gains for a cooling load.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.