Worked example
Example: Ganapathy Q4.57 case: 110,000 lb/h at 410 °F, 48 in, 50 ft. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas flow | 49,895 kg/h |
| Gas inlet temperature | 210.00 °C |
| Inside diameter | 1,219.2 mm |
| Wall thickness | 25.400 mm |
| Length (height) | 15.240 m |
| Ambient temperature | 21.110 °C |
| Wind speed | 0.50800 m/s |
| Outer surface emissivity | 90.000 % |
| Gas viscosity | 0.024000 cP |
| Gas thermal conductivity | 0.035000 W/(m·K) |
| Gas specific heat | 1.0800 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gas-side coefficient | 24.652 W/(m²·K) |
| Wall temperature (average) | 125.19 °C |
| Heat loss per outer area | 1,915.1 W/m² |
| Total heat loss | 116.45 kW |
| Gas outlet temperature | 202.22 °C |
Open this example in the calculator and change any input.
Formula
\(q = \sigma\varepsilon(T_w^4 - T_a^4) + 1.947(T_w - T_a)^{1.25}\sqrt{\frac{196.85V + 69}{69}}, \quad (T_g - T_w)h_c\frac{d_i}{d_o} = q\)
\(h_c = 0.023Re^{0.8}Pr^{0.4}\frac{k}{d_i}, \quad T_{g2} = T_{g1} - \frac{q\pi d_oH}{Wc_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W\) | Gas flow | kg/s |
| \(T_{g1}\) | Gas inlet temperature | K |
| \(d_i\) | Inside diameter | m |
| \(t\) | Wall thickness | m |
| \(H\) | Length (height) | m |
| \(T_a\) | Ambient temperature | K |
| \(V\) | Wind speed | m/s |
| \(\varepsilon\) | Outer surface emissivity | - |
| \(\mu\) | Gas viscosity | Pa·s |
| \(k\) | Gas thermal conductivity | W/(m·K) |
| \(c_p\) | Gas specific heat | J/(kg·K) |
| \(h_c\) | Gas-side coefficient | W/(m²·K) |
| \(T_w\) | Wall temperature (average) | K |
| \(q\) | Heat loss per outer area | W/m² |
| \(Q\) | Total heat loss | W |
| \(T_{g2}\) | Gas outlet temperature | K |
Method and standards
Ganapathy's casing-loss equation (radiation plus natural and wind convection, Eq. 106) converted to SI through FireCAD's unit factors, with a Dittus–Boelter gas film (exponent 0.4, as Ganapathy uses). The wall and gas outlet temperatures are solved together over one segment.
Where it is used
- Stack and duct design for low-temperature flue gas.
- Deciding on insulation.
Common mistakes
- Using the gas temperature as the wall temperature.
- Ignoring wind.
Assumptions and limits
- Thin steel wall; single segment; turbulent gas flow (a warning below Re 10 000).
- The Dittus–Boelter exponent 0.4 is the heating form; for gas being cooled the classical exponent is 0.3, about 10 % lower h_c at Pr 0.7, which would give a slightly colder wall. Gas radiation to the wall is neglected.
- The gas must stay above ambient over the length, and the wall and gas temperatures must converge; otherwise the calculation stops and asks for a shorter segment.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q4.57 (stack and duct wall temperature with and without insulation) and Eq. (106) for casing heat loss; gas-side coefficient by Dittus–Boelter
Questions and answers
Why does wall temperature matter?
If the inner wall falls below the acid dew point, sulfuric acid condenses and corrodes the steel even when the gas is well above it.
Why is the wall much colder than the gas?
The gas film coefficient is low (15–30 W/(m²·K)) compared with radiation and wind losses outside an uninsulated wall.
What do the defaults represent?
Ganapathy's case: 110,000 lb/h at 410 °F in a 48 in stack, 50 ft long, 1 in thick, 70 °F ambient.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.