Worked example
Example: Biomass 0.3 % Cl. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fuel fired | 10.000 t/h |
| Chlorine in the fuel (as fired) | 0.30000 % |
| Share of chlorine released as HCl | 60.000 % |
| Flue gas flow (dry, normal) | 100,000 Nm³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| HCl formed | 18.512 kg/h |
| HCl concentration (dry, normal) | 185.12 mg/Nm³ |
| HCl by volume (dry) | 113.81 ppm |
Open this example in the calculator and change any input.
Formula
\(\dot m_{HCl} = \dot m_f\,Cl\,f\,\frac{M_{HCl}}{M_{Cl}}, \quad c = \frac{\dot m_{HCl}}{\dot V_n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_f\) | Fuel fired | kg/s |
| \(Cl\) | Chlorine in the fuel (as fired) | - |
| \(f\) | Share of chlorine released as HCl | - |
| \(\dot V_n\) | Flue gas flow (dry, normal) | Nm³/s |
| \(\dot m_{HCl}\) | HCl formed | kg/s |
| \(c_{HCl}\) | HCl concentration (dry, normal) | kg/m³ |
| \(y_{HCl}\) | HCl by volume (dry) | - |
Method and standards
Mass balance of chlorine: the share released as HCl is converted with the molar masses of HCl and Cl; the volume fraction uses the ideal-gas molar volume at 0 °C and 101.325 kPa.
Where it is used
- Emission estimates.
- Acid gas control design.
Common mistakes
- Chlorine on dry basis with as-fired fuel.
Assumptions and limits
- Dry, normal basis, at the actual O₂ of the gas: not corrected to a reference O₂. Correct it with the emission O₂ correction calculator before comparing with a limit.
- The flue gas flow is your input and is not checked against the fuel fired; take it from the combustion calculator for the same fuel and excess air.
- The release share depends on the fuel; 60 % is a starting value, not a published figure.
References
- Mass balance Cl → HCl (molar masses, IUPAC); ppm on the molar volume at 0 °C
- 1 atm
Questions and answers
Does all chlorine become HCl?
No: much is captured as potassium and sodium chloride in ash, especially in biomass.
Why care?
HCl is regulated and corrosive below its dew point; chlorides attack superheaters.
Slop and husk?
Both can carry significant chlorine; analyse the fuel.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.