Worked example
Example: ESP 60 m³/s, w 0.08 m/s, 4 000 m². The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas flow through the ESP (actual) | 216,000 m³/h |
| Effective migration velocity | 0.080000 m/s |
| Collecting plate area | 4,000.0 m² |
| Target efficiency (for the area required) | 99.500 % |
| Dust at the ESP inlet | 40,000 mg/Nm³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Collection efficiency | 99.517 % |
| Dust at the ESP outlet | 193.12 mg/Nm³ |
| Plate area for the target efficiency | 3,973.7 m² |
| Specific collecting area A/Q | 66.667 m²/(m³/s) |
| Penetration | 0.48279 % |
Open this example in the calculator and change any input.
Formula
\(\eta = 1 - e^{-w A / Q} \qquad A_{req} = -\frac{Q\,\ln(1 - \eta_t)}{w} \qquad SCA = \frac{A}{Q} \qquad c_{out} = c_{in}(1 - \eta)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | gas flow through the ESP, actual | m³/s |
| \(w\) | effective migration velocity | m/s |
| \(A\) | collecting plate area | m² |
| \(\eta_t\) | target efficiency | – |
| \(c_{in}\) | dust at the ESP inlet | kg/m³ |
| \(\eta\) | collection efficiency | – |
| \(c_{out}\) | dust at the ESP outlet | kg/m³ |
| \(A_{req}\) | plate area for the target efficiency | m² |
| \(SCA\) | specific collecting area | s/m |
| \(1 - \eta\) | penetration | – |
Method and standards
The Deutsch–Anderson equation for the collection efficiency of an electrostatic precipitator, with an effective migration velocity that lumps the electrical and particle properties (Deutsch 1922; White, Industrial Electrostatic Precipitation, 1963).
Where it is used
- Sizing ESP collecting area.
- Estimating efficiency after a coal change.
- Planning ESP upgrades.
Common mistakes
- Using a migration velocity from another dust.
- Ignoring gas flow distribution.
- Forgetting sneakage and rapping losses.
Assumptions and limits
- Effective migration velocity from experience; the equation itself does not predict it.
- Uniform gas distribution and no re-entrainment or sneakage; real ESPs fall short of the ideal at very high efficiencies.
- The outlet concentration is on the same basis (dry or wet, reference conditions) as the inlet value; the mg/Nm³ unit shown is only a label for that basis.
- A note appears above 99.9 %, where real ESPs fall short of the ideal.
- SCA is shown in s/m (m² per m³/s) in every unit system; for ft² per 1000 acfm multiply by 5.08.
References
- Deutsch (1922); Anderson; White
- Industrial Electrostatic Precipitation (1963)
Questions and answers
How efficient is an ESP?
η = 1 − exp(−w·A/Q). With 4 000 m² of plates, 60 m³/s of gas and a migration velocity of 0.08 m/s the efficiency is 99.52 %, so 40 g/Nm³ at the inlet leaves 193 mg/Nm³.
Where does the migration velocity come from?
From the ESP maker or from tests on a similar plant and dust. It depends strongly on the dust's resistivity and particle size, which is why high-ash Indian coals need large ESPs.
How much area for 99.5 %?
A = −Q·ln(1 − η)/w. For 60 m³/s at 0.08 m/s that is 3 974 m².
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.