Worked example
Example: Ganapathy: 1000 psia, 1.5 in, 600,000 lb/(ft2 h), x 0.2 (2.43e6 Btu/(ft2 h)). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pressure (absolute) | 68.948 bar |
| Tube inside diameter | 38.100 mm |
| Mass velocity inside the tube | 813.74 kg/(m²·s) |
| Steam quality | 20.000 % |
| Design reduction from the correlation | 30.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Latent heat | 1,511.9 kJ/kg |
| Critical heat flux in the tube (Macbeth) | 7,684.4 kW/m² |
| Critical heat flux in pool boiling (Mostinski) | 3,850.9 kW/m² |
| Allowable tube heat flux after the reduction | 5,379.0 kW/m² |
Open this example in the calculator and change any input.
Formula
\(q_c = 0.00633\times10^6\,h_{fg}\,d_i^{-0.1}\left(\frac{G}{10^6}\right)^{0.51}(1 - x)\ \ (\mathrm{Btu/(ft^2\,h)};\ h_{fg}\ \mathrm{Btu/lb},\ d_i\ \mathrm{in},\ G\ \mathrm{lb/(ft^2\,h)})\)
\(q_c = 803\,p_c\left(\frac{p}{p_c}\right)^{0.35}\left(1 - \frac{p}{p_c}\right)^{0.9}\ \ (p\ \mathrm{psia}), \qquad q_{allow} = q_{c,Macbeth}(1 - m)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Pressure (absolute) | Pa |
| \(d_i\) | Tube inside diameter | m |
| \(G\) | Mass velocity inside the tube | kg/(m²·s) |
| \(x\) | Steam quality | - |
| \(m\) | Design reduction from the correlation | - |
| \(h_{fg}\) | Latent heat | J/kg |
| \(q_{c,Macbeth}\) | Critical heat flux in the tube (Macbeth) | W/m² |
| \(q_{c,Mostinski}\) | Critical heat flux in pool boiling (Mostinski) | W/m² |
| \(q_{allow}\) | Allowable tube heat flux after the reduction | W/m² |
Method and standards
Macbeth and Mostinski correlations (US units, converted).
Where it is used
- Water-wall and generating-tube checks.
- Fire-tube boiler heat flux limits.
Common mistakes
- Comparing average instead of peak flux.
- Ignoring the design reduction.
Assumptions and limits
- Water; subcritical. The data range of the Macbeth correlation is not checked: at high mass velocity and low quality it can give very high values, so use the maker's DNB data for design.
- Unit conversions: 1 Btu/(ft²·h) = 3.154591 W/m², 1 Btu/lb = 2326 J/kg, 1 in = 0.0254 m, 1 lb/(ft²·h) = 1.356230 × 10⁻³ kg/(m²·s), 1 psi = 6894.757 Pa.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1994)
- Q4.47a (Macbeth correlation) and Q4.47b (Mostinski, pool boiling); IAPWS-IF97 latent heat
Questions and answers
What do Ganapathy's examples give?
Macbeth at 1,000 psia, 1.5 in tube, 600,000 lb/(ft²·h), 20 % quality: 2.43 × 10⁶ Btu/(ft²·h) (7.7 MW/m²); Mostinski at 400 psia: 1.10 × 10⁶ Btu/(ft²·h).
Why does quality lower the critical flux?
With more vapour, the liquid film on the wall is thinner and dries out at a lower heat flux.
Is the boiler at risk?
Compare the peak local heat flux (water-wall flux × peaking factor) with the allowable value.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.