Worked example
Example: Ganapathy: 50,000 lb/h at 250 °F in 2.9 in. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow per tube (or per pass) | 22,680 kg/h |
| Tube inner diameter | 73.660 mm |
| Mean water temperature | 121.11 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water velocity | 1.5690 m/s |
| Tube-side coefficient | 9,149.7 W/(m²·K) |
Open this example in the calculator and change any input.
Formula
\(h_i = (150 + 1.55\,t)\,\frac{V^{0.8}}{d_i^{0.2}} \ \ (\mathrm{Btu/ft^2\,h\,°F};\ t\ °F,\ V\ ft/s,\ d_i\ in)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W\) | Water flow per tube (or per pass) | kg/s |
| \(d_i\) | Tube inner diameter | m |
| \(t\) | Mean water temperature | K |
| \(V\) | Water velocity | m/s |
| \(h_i\) | Tube-side coefficient | W/(m²·K) |
Method and standards
Ganapathy's Eq. (13).
Where it is used
- Economiser and water heater design.
- Quick checks of vendor data.
Common mistakes
- Using it for laminar flow.
- Entering total flow for a multi-tube pass.
Assumptions and limits
Ganapathy's expression is dimensional (°F, ft/s, inches, Btu/(ft²·h·°F)); the page converts to and from SI through the unit registry.
Turbulent flow only. No Reynolds number is computed; the page warns below about 0.3 m/s, where the flow may not be turbulent.
Turbulent single-phase water.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q4.03b
- Eq. (13)
- Water specific volume from IAPWS-IF97 (saturated liquid at t)
Questions and answers
Where does it come from?
Dittus–Boelter with water's properties folded into (150 + 1.55 t), t in °F.
What does Ganapathy's example give?
50,000 lb/h at 250 °F in a 2.9 in bore: about 1,590 Btu/ft²·h·°F with his rounded velocity of 5.05 ft/s; the exact bore area gives 5.15 ft/s and about 1,610 (9.1 kW/m²·K).
Why does it barely matter?
Gas-side coefficients are 10–100 times lower, so the overall U is set by the gas side.