FireCADCalc

Hot Water Storage: Heat-Up Time and Energy

Time and energy to heat a hot water storage tank from one temperature to another with a heater of given power and efficiency, with water from IF97.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: 2000 L, 15 to 60 °C, 24 kWCanteen 500 L, 20 to 80 °C, 9 kW

Results

Water enthalpies from IAPWS-IF97 at 3 bar(a); a stratified tank delivers hot water before the whole volume is heated.

Water mass (density at the start)1,998.4kg
Heat to the water104.43kWh
Energy input109.92kWh
Heat-up time4.5801h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2000 L, 15 to 60 °C, 24 kW. The inputs, in the units selected above:

InputValue
Tank volume2,000.0 L
Starting temperature15.000 °C
Final temperature60.000 °C
Heater power (input)24.000 kW
Heater efficiency (including losses)95.000 %

Applying the formula below gives:

ResultValue
Water mass (density at the start)1,998.4 kg
Heat to the water104.43 kWh
Energy input109.92 kWh
Heat-up time4.5801 h

Open this example in the calculator and change any input.

Formula

\(Q = m(h_2 - h_1), \quad t = \frac{Q}{\eta P}\)

Variables

Symbol Meaning SI unit
\(V\) Tank volume m³
\(T_1\) Starting temperature K
\(T_2\) Final temperature K
\(P\) Heater power (input) W
\(\eta\) Heater efficiency (including losses) -
\(m\) Water mass (density at the start) kg
\(Q\) Heat to the water J
\(E\) Energy input J
\(t\) Heat-up time s

Method and standards

Energy balance.

Where it is used

  • Colony and canteen hot water.
  • Process water heating.

Common mistakes

  • Litres taken as kg at high temperature.
  • Ignoring standing losses.

Assumptions and limits

  • Fully mixed tank.

References

  • Q = m (h₂ − h₁) with IAPWS-IF97 enthalpies

Questions and answers

2000 L from 15 to 60 °C with 24 kW?

About 104 kWh of heat: roughly 4.6 h at 95 %.

Why use enthalpy, not 4.186 kJ/kg K?

It is the same within a fraction of a per cent here; the IF97 route is exact.

Steam coil heaters?

Enter the coil duty as the power.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.