Chilled or Hot Water Closed Loop: Pump Head and Power

Pump head of a closed chilled or hot water loop from pipe friction (Colebrook), fittings and the pressure drops of chiller, coil and valve, with pump power.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: Chilled water 120 m³/h in DN150Hot water 30 m³/h in DN80 at 80 °C

Results

A closed loop has no static lift: the pump overcomes friction only. Water properties at 5 bar(a) from IAPWS.

Velocity1.7872m/s
Reynolds number210,935
Darcy friction factor0.017563
Pipe and fittings136.68kPa
Pump head29.236m
Electrical power14.702kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Chilled water 120 m³/h in DN150. The inputs, in the units selected above:

InputValue
Water flow120.00 m³/h
Pipe inside diameter154.10 mm
Pipe length, supply and return400.00 m
Pipe roughness0.045000 mm
Sum of fitting loss coefficients40.000 -
Equipment drops (chiller, coil, valve, strainer)150.00 kPa
Water temperature10.000 °C
Pump and motor efficiency65.000 %

Applying the formula below gives:

ResultValue
Velocity1.7872 m/s
Reynolds number210,935
Darcy friction factor0.017563
Pipe and fittings136.68 kPa
Pump head29.236 m
Electrical power14.702 kW

Open this example in the calculator and change any input.

Formula

\(H = \frac{(f L/D + \Sigma K)\rho v^2/2 + \Delta p_e}{\rho g}, \quad P = \frac{\rho g \dot V H}{\eta}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Water flow m³/s
\(D\) Pipe inside diameter m
\(L\) Pipe length, supply and return m
\(\varepsilon\) Pipe roughness m
\(\Sigma K\) Sum of fitting loss coefficients -
\(\Delta p_e\) Equipment drops (chiller, coil, valve, strainer) Pa
\(T\) Water temperature K
\(\eta\) Pump and motor efficiency -
\(v\) Velocity m/s
\(Re\) Reynolds number -
\(f\) Darcy friction factor -
\(\Delta p_p\) Pipe and fittings Pa
\(H\) Pump head m
\(P\) Electrical power W

Method and standards

Darcy–Weisbach.

Where it is used

  • Chilled and hot water pump selection.
  • Cooling water loops.

Common mistakes

  • Adding static height.
  • Using only one way of the loop.

Assumptions and limits

  • Single index circuit, steady flow.

References

  • Darcy–Weisbach with Colebrook friction; water properties IAPWS-IF97 and IAPWS 2008 viscosity

Questions and answers

120 m³/h in DN150, 400 m, ΣK 40, 150 kPa of equipment?

About 1.8 m/s; roughly 29 m of head and 15 kW.

Why no static head?

In a closed loop the water column on the way up balances the way down.

Index circuit?

Use the path with the highest drop; other branches are balanced to it.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.