FireCADCalc

Hydronic Pipe Sizing by Friction Rate

Water flow for a heating or chilled-water load, and the pipe diameter and velocity that give a chosen friction rate (Darcy–Weisbach with Colebrook).

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 100 kW chilled water, 6 K, 300 Pa/mHeating main 1 MW, 20 K, 150 Pa/m

Results

Typical design friction rates are 100–400 Pa/m with velocities of 0.5–1.5 m/s in small pipes and up to 3 m/s in mains. Pick the next larger standard bore.

Water mass flow3.9777kg/s
Water volume flow14.334m³/h
Pipe inside diameter62.613mm
Velocity1.2931m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 kW chilled water, 6 K, 300 Pa/m. The inputs, in the units selected above:

InputValue
Heat load100.00 kW
Water temperature difference6.0000 K
Water specific heat4.1900 kJ/(kg·K)
Water density999.00 kg/m³
Water viscosity1.3000 cP
Friction rate300.00 Pa/m
Pipe roughness0.045000 mm

Applying the formula below gives:

ResultValue
Water mass flow3.9777 kg/s
Water volume flow14.334 m³/h
Pipe inside diameter62.613 mm
Velocity1.2931 m/s

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{Q}{c_p\Delta T}, \quad \frac{\Delta p}{L} = \frac{f}{D}\frac{\rho v^2}{2}\)

Variables

Symbol Meaning SI unit
\(Q\) Heat load W
\(\Delta T\) Water temperature difference K
\(c_p\) Water specific heat J/(kg·K)
\(\rho\) Water density kg/m³
\(\mu\) Water viscosity Pa·s
\(\Delta p/L\) Friction rate, in Pa/m (1 ft of water per 100 ft = 98.1 Pa/m) -
\(\varepsilon\) Pipe roughness m
\(\dot m\) Water mass flow kg/s
\(\dot V\) Water volume flow m³/s
\(D\) Pipe inside diameter m
\(v\) Velocity m/s

Method and standards

Energy balance and Darcy–Weisbach.

Where it is used

  • Chilled and heating water pipework.
  • Checking existing pipe capacity.

Common mistakes

  • Using design ΔT the plant never achieves.
  • Ignoring glycol properties.

Assumptions and limits

  • Turbulent flow; water properties entered.
  • The friction rate is in Pa/m in every unit system: 1 ft of water per 100 ft is 98.1 Pa/m, so a US figure of 4 ft/100 ft is about 390 Pa/m.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 22 (pipe sizing, Darcy–Weisbach with Colebrook)

Questions and answers

What friction rate should I use?

100–400 Pa/m is common; lower rates cut pumping energy, higher rates save pipe cost.

Why does ΔT matter so much?

Flow is inversely proportional to ΔT; a low-ΔT system needs much larger pipes and pumps.

What do the defaults represent?

A chilled-water branch with a 6 K temperature difference at a medium friction rate in steel pipe.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.