Worked example
Example: 2000 L/day, 20 to 60 °C, 5.5 kWh/m². The inputs, in the units selected above:
| Input | Value |
|---|---|
| Hot water per day | 2,000.0 L |
| Cold water temperature | 20.000 °C |
| Hot water temperature | 60.000 °C |
| Daily solar radiation on the collector plane (kWh/m² per day) | 5.5000 - |
| Average system efficiency | 45.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat per day | 92.725 kWh |
| Collector area | 37.465 m² |
Open this example in the calculator and change any input.
Formula
\(A = \frac{\rho V (h_h - h_c)}{\eta H}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Hot water per day | m³ |
| \(T_c\) | Cold water temperature | K |
| \(T_h\) | Hot water temperature | K |
| \(H\) | Daily solar radiation on the collector plane, in kWh/m² per day | - |
| \(\rho\) | Density of the cold water (IF97) | kg/m³ |
| \(h_h, h_c\) | Enthalpy of the hot and cold water at 3 bar(a) (IF97) | J/kg |
| \(\eta\) | Average system efficiency | - |
| \(Q\) | Heat per day | J |
| \(A\) | Collector area | m² |
Method and standards
Energy balance.
Where it is used
- Colony, hostel and canteen hot water.
- Boiler feed pre-heating.
Common mistakes
- Peak instead of daily radiation.
- Horizontal radiation for tilted collectors.
Assumptions and limits
- Daily average.
- H is entered as a number in kWh/m² per day; radiation tables in MJ/m² per day must be divided by 3.6 first, otherwise the area comes out 3.6 times too small.
References
- Energy balance A = Q/(ηH); water enthalpies from IAPWS-IF97
Questions and answers
2000 L/day from 20 to 60 °C at 5.5 kWh/m²/day, 45 %?
About 93 kWh a day: roughly 37.5 m² of collector.
What efficiency?
System average over the day, including tank and pipe losses.
Cloudy days?
Keep an electric or steam backup.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.