Worked example
Example: COP 5.6. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Value given | COP |
| Value | 5.6000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| COP | 5.6000 |
| kW per ton of refrigeration | 0.62801 |
| EER (Btu/h per W) | 19.108 |
Open this example in the calculator and change any input.
Formula
\(\frac{kW}{TR} = \frac{3.516\,853}{COP}, \quad EER = 3.412\,142\, COP\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{given}\) | Value given | - |
| \(x\) | Value | - |
| \(COP\) | COP | - |
| \(kW/TR\) | kW per ton of refrigeration | - |
| \(EER\) | EER (Btu/h per W) | - |
Method and standards
Unit definitions.
Where it is used
- Comparing chiller offers.
- Energy audits.
Common mistakes
- Comparing ratings at different conditions.
- Including or excluding auxiliaries inconsistently.
Assumptions and limits
- Same basis for all values.
References
- Definitions: 1 TR = 12 000 Btu/h = 3.516 853 kW; 1 Btu (IT) = 1055.055 852 62 J
Questions and answers
COP 5.6?
0.628 kW/TR, EER 19.1.
0.6 kW/TR?
COP 5.86.
Is EER the same as SEER?
No; SEER is a seasonal figure for unitary equipment.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.