FireCADCalc

Tons of Refrigeration, kW/TR, COP and EER

Converts refrigeration capacity between TR, kW and Btu/h, and gives kW per TR, COP and EER from the compressor or chiller power input.

Food, dairy and textileAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 300 TR chiller, 195 kW100 kW cooling, 30 kW inputSplit unit 5.3 kW, 1.6 kW

Results

1 TR = 12 000 Btu/h = 3.517 kW (the US ton: 2000 lb of ice melted in 24 h).

Capacity in kW1,055.1kW
Capacity in TR300.00TR
Capacity in Btu/h3,600,000Btu/h
Power per ton of refrigeration (kW/TR)0.65000
Coefficient of performance5.4105
Energy efficiency ratio (Btu/h per W)18.462

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 300 TR chiller, 195 kW. The inputs, in the units selected above:

InputValue
Refrigeration capacity300.00 TR
Electrical power input195.00 kW

Applying the formula below gives:

ResultValue
Capacity in kW1,055.1 kW
Capacity in TR300.00 TR
Capacity in Btu/h3,600,000 Btu/h
Power per ton of refrigeration (kW/TR)0.65000
Coefficient of performance5.4105
Energy efficiency ratio (Btu/h per W)18.462

Open this example in the calculator and change any input.

Formula

\(\dot Q_e[\text{TR}] = \frac{\dot Q_e}{3516.85} \qquad \text{kW/TR} = \frac{\dot W/1000}{\dot Q_e[\text{TR}]} \qquad COP = \frac{\dot Q_e}{\dot W} \qquad EER = \frac{\dot Q_e[\text{Btu/h}]}{\dot W}\)

Variables

Symbol Meaning SI unit
\(\dot Q_e\) refrigeration capacity W
\(\dot W\) electrical power input W
\(\text{kW/TR}\) power per ton of refrigeration kW/TR
\(COP\) coefficient of performance –
\(EER\) energy efficiency ratio Btu/(h·W)

Method and standards

Definitions; 1 TR = 12 000 Btu/h with the International Table Btu (NIST SP 811).

Where it is used

  • Chiller performance monitoring.
  • Comparing chiller offers.
  • Energy audits of refrigeration plants.

Common mistakes

  • Comparing compressor-only kW/TR with whole-plant kW/TR.
  • Mixing the metric ton of refrigeration with TR.
  • Using rated capacity instead of measured capacity.

Assumptions and limits

  • The US (12 000 Btu/h) ton.

References

  • NIST SP 811 (ton of refrigeration = 12 000 Btu/h)

Questions and answers

What is the kW/TR of a 300 TR chiller drawing 195 kW?

0.65 kW/TR, a COP of 5.41 and an EER of 18.5 Btu/h per W.

How many kW is one ton of refrigeration?

3.517 kW: 12 000 Btu/h, the heat to melt 2000 lb of ice in 24 hours.

Is lower kW/TR better?

Yes. kW/TR is the inverse of COP: 3.517 / COP.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.