Worked example
Example: 300 TR chiller, 195 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Refrigeration capacity | 300.00 TR |
| Electrical power input | 195.00 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacity in kW | 1,055.1 kW |
| Capacity in TR | 300.00 TR |
| Capacity in Btu/h | 3,600,000 Btu/h |
| Power per ton of refrigeration (kW/TR) | 0.65000 |
| Coefficient of performance | 5.4105 |
| Energy efficiency ratio (Btu/h per W) | 18.462 |
Open this example in the calculator and change any input.
Formula
\(\dot Q_e[\text{TR}] = \frac{\dot Q_e}{3516.85} \qquad \text{kW/TR} = \frac{\dot W/1000}{\dot Q_e[\text{TR}]} \qquad COP = \frac{\dot Q_e}{\dot W} \qquad EER = \frac{\dot Q_e[\text{Btu/h}]}{\dot W}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_e\) | refrigeration capacity | W |
| \(\dot W\) | electrical power input | W |
| \(\text{kW/TR}\) | power per ton of refrigeration | kW/TR |
| \(COP\) | coefficient of performance | – |
| \(EER\) | energy efficiency ratio | Btu/(h·W) |
Method and standards
Definitions; 1 TR = 12 000 Btu/h with the International Table Btu (NIST SP 811).
Where it is used
- Chiller performance monitoring.
- Comparing chiller offers.
- Energy audits of refrigeration plants.
Common mistakes
- Comparing compressor-only kW/TR with whole-plant kW/TR.
- Mixing the metric ton of refrigeration with TR.
- Using rated capacity instead of measured capacity.
Assumptions and limits
- The US (12 000 Btu/h) ton.
References
- NIST SP 811 (ton of refrigeration = 12 000 Btu/h)
Questions and answers
What is the kW/TR of a 300 TR chiller drawing 195 kW?
0.65 kW/TR, a COP of 5.41 and an EER of 18.5 Btu/h per W.
How many kW is one ton of refrigeration?
3.517 kW: 12 000 Btu/h, the heat to melt 2000 lb of ice in 24 hours.
Is lower kW/TR better?
Yes. kW/TR is the inverse of COP: 3.517 / COP.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.