Cold Room Pull-Down Time

Time for a refrigeration plant to cool a room's product from a start to a target temperature against wall heat gain, and the lowest temperature the plant can hold.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: 5 t product, 20 kW, UA 200 W/K, 30 → 2 °CDairy 2 t at 3,900 J/kgK, 15 kW, UA 300

Results

Lumped capacity with constant capacity and wall gain UA(t_a − t). Capacity actually falls as the room cools (lower suction pressure); use the capacity at the target temperature for a conservative answer. Sensible cooling only (no freezing).

Lowest temperature the plant can hold-65.000°C
Time constant mc/UA25.000h
Pull-down time8.7296h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 t product, 20 kW, UA 200 W/K, 30 → 2 °C. The inputs, in the units selected above:

InputValue
Product mass (plus equivalent of structure)5,000.0 kg
Product specific heat (above freezing)3.6000 kJ/(kg·K)
Refrigeration capacity20.000 kW
Room heat gain coefficient0.20000 kW/K
Ambient temperature35.000 °C
Start temperature30.000 °C
Target temperature2.0000 °C

Applying the formula below gives:

ResultValue
Lowest temperature the plant can hold-65.000 °C
Time constant mc/UA25.000 h
Pull-down time8.7296 h

Open this example in the calculator and change any input.

Formula

\(t = \frac{mc}{UA}\ln\frac{Q_r - UA(t_a - t_0)}{Q_r - UA(t_a - t_1)}\)

Variables

Symbol Meaning SI unit
\(m_p\) Product mass (plus equivalent of structure) kg
\(c_p\) Product specific heat (above freezing) J/(kg·K)
\(Q_r\) Refrigeration capacity W
\(UA\) Room heat gain coefficient W/K
\(t_a\) Ambient temperature K
\(t_0\) Start temperature K
\(t_1\) Target temperature K
\(t_{min}\) Lowest temperature the plant can hold K
\(\tau\) Time constant mc/UA s
\(t\) Pull-down time s

Method and standards

Lumped transient balance.

Where it is used

  • Cold store commissioning.
  • Checking plant size for loading cycles.

Common mistakes

  • Ignoring structure and air mass.
  • Using rated capacity at the start temperature.

Assumptions and limits

  • Uniform product temperature.
  • Constant refrigeration capacity: real capacity falls as the room cools, so the actual pull-down is slower; enter the capacity at the target temperature for a conservative time.

References

  • Lumped energy balance mc dT/dt = −Q_r + UA(T_a − T) (heat transfer definitions)

Questions and answers

Why does pull-down slow near the target?

Wall heat gain grows as the room gets colder, leaving less capacity to cool the product.

What limits the lowest temperature?

When wall gain equals plant capacity: t_min = t_a − Q_r/UA.

What do the defaults represent?

Five tonnes of fruit-like product cooled from 30 °C to 2 °C in a room with modest wall gain.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.