Worked example
Example: 100 kW chiller: 400 / 430 / 250 kJ/kg. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Refrigerating capacity | 100.00 kW |
| Enthalpy at compressor suction | 400.00 kJ/kg |
| Enthalpy at compressor discharge | 430.00 kJ/kg |
| Enthalpy leaving the condenser (= h₄ after the expansion valve) | 250.00 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Refrigerating effect h₁ − h₄ | 150.00 kJ/kg |
| Compressor work h₂ − h₁ | 30.000 kJ/kg |
| Refrigerant flow | 2,400.0 kg/h |
| Compressor power (to the refrigerant) | 20.000 kW |
| Heat rejected in the condenser | 120.00 kW |
| Coefficient of performance | 5.0000 |
| Power per ton of refrigeration | 0.70337 |
Open this example in the calculator and change any input.
Formula
\(q_e = h_1 - h_4, \quad w = h_2 - h_1, \quad \dot m = \frac{\dot Q_e}{q_e}\)
\(COP = \frac{h_1 - h_4}{h_2 - h_1}, \quad \dot Q_c = \dot m (h_2 - h_3)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_e\) | Refrigerating capacity | W |
| \(h_1\) | Enthalpy at compressor suction | J/kg |
| \(h_2\) | Enthalpy at compressor discharge | J/kg |
| \(h_3\) | Enthalpy leaving the condenser (= h₄ after the expansion valve) | J/kg |
| \(q_e\) | Refrigerating effect h₁ − h₄ | J/kg |
| \(w\) | Compressor work h₂ − h₁ | J/kg |
| \(\dot m\) | Refrigerant flow | kg/s |
| \(P\) | Compressor power (to the refrigerant) | W |
| \(\dot Q_c\) | Heat rejected in the condenser | W |
| \(COP\) | Coefficient of performance | - |
| \(kW/TR\) | Power per ton of refrigeration | - |
Method and standards
Steady energy balance on each component; the expansion valve is isenthalpic (h₄ = h₃).
Where it is used
- Chiller and cold store checks.
- Refrigeration examinations.
- Comparing refrigerants.
Common mistakes
- Using h₃ ≠ h₄.
- Mixing enthalpy references.
- Power to refrigerant taken as motor power.
Assumptions and limits
- Ideal compressor power to the refrigerant; no line losses.
References
- Vapour compression cycle energy balance (ASHRAE Handbook—Fundamentals, ch. 2)
Questions and answers
What COP for 400, 430 and 250 kJ/kg?
Refrigerating effect 150 kJ/kg, work 30 kJ/kg: COP 5.0, which is 0.70 kW/TR.
What flow for 100 kW?
0.667 kg/s of refrigerant, needing 20 kW of compression and rejecting 120 kW.
Why must the enthalpies come from one chart?
Different tables use different reference states.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.