Refrigerant Compressor Power and Discharge Enthalpy

Discharge enthalpy, isentropic and shaft power and electrical input of a refrigerant compressor from table enthalpies, mass flow and efficiencies.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: 400 → 430 kJ/kg, η 0.7, 0.5 kg/sAmmonia 1,450 → 1,700 kJ/kg, 0.2 kg/s

Results

Read h₁ at suction pressure and temperature and h₂s at discharge pressure and the suction entropy from the refrigerant's tables or chart. Then the discharge temperature is the table temperature at discharge pressure and h₂.

Actual discharge enthalpy442.86kJ/kg
Isentropic power15.000kW
Shaft power21.429kW
Electrical input23.292kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400 → 430 kJ/kg, η 0.7, 0.5 kg/s. The inputs, in the units selected above:

InputValue
Suction enthalpy400.00 kJ/kg
Isentropic discharge enthalpy430.00 kJ/kg
Isentropic efficiency70.000 %
Refrigerant mass flow1,800.0 kg/h
Motor and drive efficiency92.000 %

Applying the formula below gives:

ResultValue
Actual discharge enthalpy442.86 kJ/kg
Isentropic power15.000 kW
Shaft power21.429 kW
Electrical input23.292 kW

Open this example in the calculator and change any input.

Formula

\(h_2 = h_1 + \frac{h_{2s} - h_1}{\eta_s}, \quad W = \frac{\dot m(h_{2s} - h_1)}{\eta_s}, \quad W_e = \frac{W}{\eta_m}\)

Variables

Symbol Meaning SI unit
\(h_1\) Suction enthalpy J/kg
\(h_{2s}\) Isentropic discharge enthalpy J/kg
\(\eta_s\) Isentropic efficiency -
\(\dot m\) Refrigerant mass flow kg/s
\(\eta_m\) Motor and drive efficiency -
\(h_2\) Actual discharge enthalpy J/kg
\(W_s\) Isentropic power W
\(W\) Shaft power W
\(W_e\) Electrical input W

Method and standards

Compression process.

Where it is used

  • Compressor selection checks.
  • Discharge temperature limits.

Common mistakes

  • Using saturated instead of superheated suction enthalpy.
  • Mixing kJ/kg and kcal/kg.

Assumptions and limits

  • Steady adiabatic compression.

References

  • ASHRAE Handbook—Refrigeration (2018)
  • ch. 2 (compression process: h₂ = h₁ + (h₂s − h₁)/η_s)

Questions and answers

Where do the enthalpies come from?

From the refrigerant's p–h chart or tables: suction state, then along constant entropy to discharge pressure.

Why is actual discharge hotter?

Losses add heat to the gas; lower isentropic efficiency gives a hotter discharge and more power.

What do the defaults represent?

A mid-size compressor with enthalpies typical of an HFC at air-conditioning conditions.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.