Worked example
Example: 350 kW open drive, COP 4.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Refrigeration capacity | 350.00 kW |
| COP on compressor shaft power | 4.5000 - |
| Compressor type | Open drive (motor outside) |
| Motor efficiency | 92.000 % |
| Condenser water temperature rise | 5.0000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Compressor shaft power | 77.778 kW |
| Condenser heat rejection | 427.78 kW |
| Heat rejection factor Q_c/Q_e | 1.2222 |
| Condenser water flow | 73.579 t/h |
Open this example in the calculator and change any input.
Formula
\(Q_c = Q_e + W\ \text{(open)}, \quad Q_c = Q_e + \frac{W}{\eta_m}\ \text{(hermetic)}, \quad HRF = \frac{Q_c}{Q_e}, \quad \dot m_w = \frac{Q_c}{c_p \Delta T_w},\ c_p = 4186\ \mathrm{J/(kg\,K)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_e\) | Refrigeration capacity | W |
| \(COP\) | COP on compressor shaft power | - |
| \(\text{compressor}\) | Compressor type | - |
| \(\eta_m\) | Motor efficiency | - |
| \(\Delta T_w\) | Condenser water temperature rise | K |
| \(W\) | Compressor shaft power | W |
| \(Q_c\) | Condenser heat rejection | W |
| \(HRF\) | Heat rejection factor Q_c/Q_e | - |
| \(\dot m_w\) | Condenser water flow | kg/s |
Method and standards
Energy balance.
Where it is used
- Cooling tower and condenser sizing.
- Heat recovery from condensers.
Common mistakes
- Sizing the tower on refrigeration capacity alone.
- Ignoring motor heat in hermetic units.
Assumptions and limits
- Steady state; heat lost from the compressor shell and discharge line is ignored (all compressor work goes to the condenser).
- Condenser water c_p 4186 J/(kg·K).
References
- ASHRAE Handbook—Refrigeration (2018)
- ch. 39 (condensers: Q_c = Q_e + W)
Questions and answers
Why is the condenser bigger than the evaporator?
It rejects the evaporator heat plus the compressor work, typically 1.2–1.3 times the capacity.
Why do hermetic compressors add more?
Motor losses heat the suction gas, so they too end up in the condenser.
What do the defaults represent?
A 350 kW (about 100 TR) water-cooled chiller with a hermetic-or-open choice and a 5 K water rise.