Worked example
Example: 2000 TR·h, 85 % usable. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling to store | 2,000.0 TR·h |
| Latent heat of fusion of ice | 333.50 kJ/kg |
| Usable share of the ice (melt-out) | 85.000 % |
| Ice density | 917.00 kg/m³ |
| Ice share of the tank volume (packing) | 50.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Ice mass | 89.325 t |
| Ice volume | 97.410 m³ |
| Tank volume | 194.82 m³ |
Open this example in the calculator and change any input.
Formula
\(m = \frac{Q}{L u}, \quad V_t = \frac{m}{\rho_i \phi}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Cooling to store | J |
| \(L\) | Latent heat of fusion of ice | J/kg |
| \(u\) | Usable share of the ice (melt-out) | - |
| \(\rho_i\) | Ice density | kg/m³ |
| \(\phi\) | Ice share of the tank volume (packing) | - |
| \(m\) | Ice mass | kg |
| \(V_i\) | Ice volume | m³ |
| \(V_t\) | Tank volume | m³ |
Method and standards
Latent heat.
Where it is used
- Peak shaving of chiller plants.
- Process cooling buffers.
Common mistakes
- Assuming full melt-out.
- Ignoring tank packing.
Assumptions and limits
- Latent storage.
References
- Latent heat storage m = Q/(L u)
Questions and answers
2000 TR·h with 85 % usable?
About 89 t of ice, 97 m³ of ice in about 195 m³ of tank.
Why not 100 % usable?
Ice far from the coils melts slowly and some stays at the end of the cycle.
Chiller penalty?
Making ice lowers the chiller's evaporating temperature and COP.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.