Worked example
Example: Chiller room 6 x 5 x 3 m at 2 °C, 2 t/day loaded at 30 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inside length | 6.0000 m |
| Inside width | 5.0000 m |
| Inside height | 3.0000 m |
| U-value of walls, roof and floor | 0.25000 W/(m²·K) |
| Room temperature | 2.0000 °C |
| Room relative humidity | 90.000 % |
| Outside air temperature | 35.000 °C |
| Outside relative humidity | 60.000 % |
| Air changes (door openings) | 10.000 1/d |
| Product loaded per day | 2,000.0 kg |
| Product temperature when loaded | 30.000 °C |
| Specific heat of the product above freezing | 3.6000 kJ/(kg·K) |
| Freezing point of the product | -2.0000 °C |
| Latent heat of freezing of the product | 250.00 kJ/kg |
| Specific heat of the product below freezing | 1.8000 kJ/(kg·K) |
| People, lights, fans and defrost (average) | 1,500.0 W |
| Safety margin | 10.000 % |
| Compressor running hours per day | 18.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Transmission through the envelope per day | 24.948 kWh |
| Air changes per day | 24.986 kWh |
| Product cooling and freezing per day | 56.000 kWh |
| Internal loads per day | 36.000 kWh |
| Total heat per day | 141.93 kWh |
| Refrigeration capacity needed | 8.6738 kW |
| Refrigeration capacity needed, in tons of refrigeration (same as Q) | 2.4663 TR |
Open this example in the calculator and change any input.
Formula
\(E_t = U \cdot 2(LW + LH + WH)(T_o - T_r)\, t_d\)
\(E_a = L W H\, n\, t_d\, \rho_{da} (h_o - h_r)\)
\(E_p = m_p c_1 (T_{in} - T_r)\ \text{or}\ m_p [c_1 (T_{in} - T_f) + L_f + c_2 (T_f - T_r)]\)
\(Q = \frac{(E_t + E_a + E_p + E_i)(1 + k_s)}{t_r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Inside length | m |
| \(W\) | Inside width | m |
| \(H\) | Inside height | m |
| \(U\) | U-value of walls, roof and floor | W/(m²·K) |
| \(T_r\) | Room temperature | K |
| \(\varphi_r\) | Room relative humidity | - |
| \(T_o\) | Outside air temperature | K |
| \(\varphi_o\) | Outside relative humidity | - |
| \(n\) | Air changes (door openings) | 1/s |
| \(m_p\) | Product loaded per day | kg |
| \(T_{in}\) | Product temperature when loaded | K |
| \(c_1\) | Specific heat of the product above freezing | J/(kg·K) |
| \(T_f\) | Freezing point of the product | K |
| \(L_f\) | Latent heat of freezing of the product | J/kg |
| \(c_2\) | Specific heat of the product below freezing | J/(kg·K) |
| \(Q_{int}\) | People, lights, fans and defrost (average) | W |
| \(k_s\) | Safety margin | - |
| \(t_r\) | Compressor running hours per day | s |
| \(E_t\) | Transmission through the envelope per day | J |
| \(E_a\) | Air changes per day | J |
| \(E_p\) | Product cooling and freezing per day | J |
| \(E_i\) | Internal loads per day | J |
| \(E\) | Total heat per day | J |
| \(Q\) | Refrigeration capacity needed | W |
| \(Q_{TR}\) | Refrigeration capacity needed, in tons of refrigeration (same as Q) | W |
| \(t_d\) | Seconds in a day | s |
| \(\rho_{da}\) | Dry air density in the room | kg/m³ |
| \(h_o, h_r\) | Moist-air enthalpy outside and in the room | J/kg |
Method and standards
The heat entering in a day by transmission, air exchange and product, plus internal gains, is removed in the compressor running hours. Moist-air enthalpy follows ASHRAE Fundamentals ch. 1, with saturation over ice below 0 °C.
Where it is used
- Sizing condensing units for cold rooms and freezers.
- Checking an existing plant after more product or more door openings.
- Comparing panel thicknesses.
Common mistakes
- Forgetting the floor in the envelope area.
- Ignoring defrost and evaporator fan heat.
- Taking the product to room temperature in less than the time allowed.
Assumptions and limits
- Daily average; pull-down within the day.
- Respiration heat not included.
- Sea-level pressure (101 325 Pa); no altitude input. The air-change load uses the room's dry-air density and the outside enthalpy; the latent heat of frost formed on the coil is not included.
References
- ASHRAE Handbook—Refrigeration
- ch. 24 Refrigerated-facility loads (method)
- IAPWS R14-08 saturation over ice
Questions and answers
What capacity does a 6 × 5 × 3 m chiller room need?
At 2 °C with 2 t/day of produce at 30 °C, about 511 MJ a day; with 10 % margin over 18 running hours, 8.7 kW (2.5 TR).
Why so much for air changes?
Each door opening lets warm moist air in; cooling and drying it can match the wall load in a busy room.
How does a freezer differ?
Product is cooled to its freezing point, frozen (latent heat) and cooled further: 3 t/day at 5 °C into −20 °C needs 849 MJ for product alone.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.