Worked example
Example: Ammonia −35/40 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Evaporating pressure (absolute) | 0.93000 bar |
| Condensing pressure (absolute) | 15.500 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Intermediate pressure | 3.7967 bar |
| Overall pressure ratio | 16.667 |
| Pressure ratio per stage | 4.0825 |
Open this example in the calculator and change any input.
Formula
\(p_i = \sqrt{p_ep_c}, \quad r_s = \sqrt{\frac{p_c}{p_e}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_e\) | Evaporating pressure (absolute) | Pa |
| \(p_c\) | Condensing pressure (absolute) | Pa |
| \(p_i\) | Intermediate pressure | Pa |
| \(p_c/p_e\) | Overall pressure ratio | - |
| \(r_s\) | Pressure ratio per stage | - |
Method and standards
Equal pressure ratio.
Where it is used
- Freezing and cold-store plants.
- Choosing compound versus single-stage compressors.
Common mistakes
- Using gauge pressures.
- Ignoring intercooler pressure drop.
Assumptions and limits
- Ideal gas; equal stage efficiency.
References
- Geometric-mean interstage pressure p_i = √(p_ep_c) (ASHRAE Handbook—Refrigeration (2018), ch. 2, multistage systems)
Questions and answers
When are two stages needed?
When the overall pressure ratio is large (low-temperature freezing with ammonia): one stage would have poor volumetric efficiency and very hot discharge.
Is the geometric mean exact?
It is the ideal-gas optimum for equal stage efficiency; real systems with intercoolers shift it slightly.
What do the defaults represent?
An ammonia system evaporating near −35 °C and condensing near 40 °C.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.