Worked example
Example: 5 %, 2 to 12 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Clearance ratio (clearance / swept volume) | 5.0000 % |
| Suction pressure (absolute) | 2.0000 bar |
| Discharge pressure (absolute) | 12.000 bar |
| Polytropic index of re-expansion and compression | 1.1500 - |
| Suction temperature | -5.0000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pressure ratio | 6.0000 |
| Clearance volumetric efficiency | 81.252 % |
| Discharge temperature (polytropic, ideal gas) | 65.597 °C |
| Pressure ratio at which η_v falls to zero | 33.155 |
Open this example in the calculator and change any input.
Formula
\(\eta_{v,c} = 1 + c - c\left(\frac{p_2}{p_1}\right)^{1/n}, \quad T_2 = T_1\left(\frac{p_2}{p_1}\right)^{(n-1)/n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(c\) | Clearance ratio (clearance / swept volume) | - |
| \(p_1\) | Suction pressure (absolute) | Pa |
| \(p_2\) | Discharge pressure (absolute) | Pa |
| \(n\) | Polytropic index of re-expansion and compression | - |
| \(T_1\) | Suction temperature | K |
| \(r\) | Pressure ratio | - |
| \(\eta_{v,c}\) | Clearance volumetric efficiency | - |
| \(T_2\) | Discharge temperature (polytropic, ideal gas) | K |
| \(r_{max}\) | Pressure ratio at which η_v falls to zero | - |
Method and standards
Polytropic re-expansion.
Where it is used
- Refrigeration and air compressor checks.
- Examinations.
Common mistakes
- Gauge pressures.
- Using η_v,c as the actual efficiency.
Assumptions and limits
- Polytropic process, ideal gas.
- With zero clearance the limiting pressure ratio is infinite and is not shown.
References
- Clearance volumetric efficiency η_v = 1 + c − c(p₂/p₁)^(1/n); polytropic T₂/T₁ = r^((n−1)/n) (thermodynamics texts)
Questions and answers
5 % clearance, 2 to 12 bar, n 1.15?
Pressure ratio 6: η_v about 81 %.
Why does a high ratio hurt?
Clearance gas re-expands over more of the stroke before fresh gas enters.
Discharge temperature?
An ideal-gas estimate; real refrigerants need tables.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.