Product Cooling and Freezing Load

Refrigeration load to cool, freeze and sub-cool a product from specific heats above and below freezing and its latent heat, over a set pull-down time.

Food, dairy and textile

Inputs

Examples: 2 t frozen to −18 °C in 24 hChilling only, 30 to 4 °C in 12 hAlready frozen, −5 to −25 °C

From a food or product data table; your figure.

Results

Average load; the early part of a pull-down needs more. Add packaging, respiration heat and a safety margin as your practice requires.

Cooling to the freezing point64.000kWh
Freezing138.89kWh
Sub-cooling16.889kWh
Total per batch219.78kWh
Average load over the pull-down9.1574kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 t frozen to −18 °C in 24 h. The inputs, in the units selected above:

InputValue
Product mass per batch2,000.0 kg
Entering temperature30.000 °C
Freezing point-2.0000 °C
Final temperature-18.000 °C
Specific heat above freezing3.6000 kJ/(kg·K)
Latent heat of freezing of the product250.00 kJ/kg
Specific heat below freezing1.9000 kJ/(kg·K)
Pull-down time24.000 h

Applying the formula below gives:

ResultValue
Cooling to the freezing point64.000 kWh
Freezing138.89 kWh
Sub-cooling16.889 kWh
Total per batch219.78 kWh
Average load over the pull-down9.1574 kW

Open this example in the calculator and change any input.

Formula

\(Q = m\left[c_1(T_1 - T_f) + L_f + c_2(T_f - T_2)\right], \quad \dot Q = \frac{Q}{t}\)

Variables

Symbol Meaning SI unit
\(m\) Product mass per batch kg
\(T_1\) Entering temperature K
\(T_f\) Freezing point K
\(T_2\) Final temperature K
\(c_1\) Specific heat above freezing J/(kg·K)
\(L_f\) Latent heat of freezing of the product J/kg
\(c_2\) Specific heat below freezing J/(kg·K)
\(t\) Pull-down time s
\(Q_1\) Cooling to the freezing point J
\(Q_2\) Freezing J
\(Q_3\) Sub-cooling J
\(Q\) Total per batch J
\(\dot Q\) Average load over the pull-down W

Method and standards

Sensible and latent heat.

Where it is used

  • Cold store and freezer sizing.
  • Ice cream, fish, meat and vegetable plants.

Common mistakes

  • Product properties at the wrong water content.
  • No pull-down margin.

Assumptions and limits

  • Freezing at one temperature, with all the latent heat released there and the product fully frozen; real foods freeze over a range and keep some unfrozen water, so the latent part is slightly overstated at moderate final temperatures.

References

  • Sensible and latent heat Q = m[c₁(T₁ − T_f) + L_f + c₂(T_f − T₂)] (ASHRAE Handbook—Refrigeration, load calculations)

Questions and answers

2 t from 30 °C frozen to −18 °C in 24 h?

About 64 kWh to the freezing point, 139 kWh to freeze and 17 kWh to sub-cool: about 9.2 kW average.

Where do the properties come from?

Product data tables; they depend on water content.

Product already frozen?

Enter an entering temperature below the freezing point: only sub-cooling is counted.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.