Worked example
Example: Centrifugal. The inputs, in the units selected above:
| Input | Value |
|---|---|
| COP at 100 % load | 6.1000 - |
| COP at 75 % load | 7.2000 - |
| COP at 50 % load | 8.4000 - |
| COP at 25 % load | 7.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| IPLV as COP | 7.7050 |
| IPLV as kW/TR | 0.45644 |
| IPLV as EER (Btu/h per W) | 26.291 |
Open this example in the calculator and change any input.
Formula
\(IPLV = 0.01A + 0.42B + 0.45C + 0.12D, \quad IPLV_{kW/TR} = \frac{1}{0.01/k_A + 0.42/k_B + 0.45/k_C + 0.12/k_D}, \quad k_i = \frac{3.517}{COP_i}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | COP at 100 % load | - |
| \(B\) | COP at 75 % load | - |
| \(C\) | COP at 50 % load | - |
| \(D\) | COP at 25 % load | - |
| \(IPLV\) | IPLV as COP | - |
| \(IPLV_{kW/TR}\) | IPLV as kW/TR | - |
| \(k_A \ldots k_D\) | Part-load efficiencies as kW/TR, 3.517/COP | - |
| \(IPLV_{EER}\) | IPLV as EER (Btu/h per W) | - |
Method and standards
AHRI weighting.
Where it is used
- Comparing chiller offers.
- Energy code checks.
Common mistakes
- Weighting kW/TR arithmetically.
- Ratings at non-standard conditions.
Assumptions and limits
- AHRI rating conditions.
References
- AHRI Standard 550/590 IPLV weights 0.01
- 0.42
- 0.45
- 0.12 (COP weighted mean; kW/TR weighted harmonic mean)
Questions and answers
COP 6.1, 7.2, 8.4 and 7.0?
IPLV about 7.7 as COP, 0.46 kW/TR.
Why weight 50 % load most?
Chillers spend most hours there in the national-average building.
Use it for my plant's energy?
No; use your own load profile with the part-load energy calculator.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.