Balancing Valve Kv and Pressure Drop

Kv a balancing valve needs to pass a design flow at a set pressure drop, and the pressure drop across a valve of chosen Kvs at that flow.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 2.5 m³/h, 10 kPa, Kvs 4Glycol 8 m³/h, 25 kPa, Kvs 10

Metric Kv (m³/h at 1 bar) in every unit system. A US Cv converts as Kv = Cv/1.156.

Results

The selected valve is too small: even fully open it drops more than the target.

Read the handwheel setting for this Kv from the maker's chart. Aim for at least 3 kPa across the valve at design flow so the measurement is accurate.

Kv required7.9057
Pressure drop of the selected valve fully open39.062kPa
Kv fraction to set197.64%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2.5 m³/h, 10 kPa, Kvs 4. The inputs, in the units selected above:

InputValue
Design flow2.5000 m³/h
Pressure drop to absorb10.000 kPa
Specific gravity1.0000 -
Kvs of the selected valve (fully open), metric4.0000 -

Applying the formula below gives:

ResultValue
Kv required7.9057
Pressure drop of the selected valve fully open39.062 kPa
Kv fraction to set197.64 %

Open this example in the calculator and change any input.

Formula

\(K_v = \dot V\sqrt{\frac{SG}{\Delta p}}, \quad \Delta p_{open} = SG\left(\frac{\dot V}{K_{vs}}\right)^2\quad(\mathrm{m^3/h,\ bar})\)

Variables

Symbol Meaning SI unit
\(\dot V\) Design flow m³/s
\(\Delta p\) Pressure drop to absorb Pa
\(SG\) Specific gravity -
\(K_{vs}\) Kvs of the selected valve (fully open), metric -
\(K_v\) Kv required -
\(\Delta p_{open}\) Pressure drop of the selected valve fully open Pa
\(K_v/K_{vs}\) Kv fraction to set -

Method and standards

K_v definition.

Where it is used

  • Commissioning heating and chilled water.
  • Selecting balancing valve sizes.

Common mistakes

  • Valve so large it works almost closed.
  • Mixing Kv and Cv.

Assumptions and limits

  • Turbulent, non-flashing liquid.
  • Kv and Kvs are metric (m³/h at 1 bar) in every unit system; convert a US Cv by Kv = Cv/1.156.

References

  • K_v = Q√(SG/Δp)
  • Q in m³/h and Δp in bar (IEC 60534 definition of K_v)

Questions and answers

Why balance a hydronic system?

Circuits near the pump get too much water and remote ones too little; balancing valves absorb the excess head.

How much pressure drop should a balancing valve take?

Enough to measure accurately (3 kPa or more) and to absorb the circuit's excess head.

What do the defaults represent?

A terminal circuit flow with a 10 kPa excess head and a mid-size valve.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.