FireCADCalc

Brine or Glycol (Secondary Coolant) Flow for a Load

Mass and volume flow of a brine, glycol or other secondary coolant to carry a cooling load at a set temperature range, from its density and specific heat.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textile

Inputs

Examples: Glycol 100 kW, 4 KBrine 250 kW, 3 K

From the coolant maker's table at the mean temperature and concentration.

Results

Mass flow25,000kg/h
Volume flow23.810m³/h
Flow relative to water (4186 J/kg K, 1000 kg/m³)1.1074

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Glycol 100 kW, 4 K. The inputs, in the units selected above:

InputValue
Cooling load100.00 kW
Coolant temperature range4.0000 K
Coolant density1,050.0 kg/m³
Coolant specific heat3.6000 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Mass flow25,000 kg/h
Volume flow23.810 m³/h
Flow relative to water (4186 J/kg K, 1000 kg/m³)1.1074

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot Q}{c_p \Delta T}, \quad \dot V = \frac{\dot m}{\rho}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) Cooling load W
\(\Delta T\) Coolant temperature range K
\(\rho\) Coolant density kg/m³
\(c_p\) Coolant specific heat J/(kg·K)
\(\dot m\) Mass flow kg/s
\(\dot V\) Volume flow m³/s
\(\dot V/\dot V_w\) Flow relative to water (4186 J/kg K, 1000 kg/m³) -

Method and standards

Energy balance.

Where it is used

  • Glycol chillers and cold stores.
  • Brine ice plants.

Common mistakes

  • Water properties for glycol.
  • Properties at the wrong concentration.

Assumptions and limits

  • Constant properties.

References

  • Energy balance ṁ = Q/(c_p ΔT)

Questions and answers

100 kW with a 4 K range, ρ 1050, c_p 3600?

About 25,000 kg/h, 23.8 m³/h: 11 % more than water.

Why more flow than water?

Glycol mixes have lower specific heat.

Pump power?

Rises further because glycol is more viscous.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.