Rectangular Duct: Friction, Nusselt Number and Wall Heating

Hydraulic diameter, Reynolds number, friction factor, Nusselt number, NTU, outlet temperature and pressure drop for flow in a rectangular duct with heated walls.

Thermal power plantChemical and fertiliser

Inputs

Examples: Same flow in the square 70.71 mm ductWater in a 320 x 40 micrometre microchannel, 15 mm long (laminar)

Accepted: 0.01 to 5,000 mm
Accepted: 0.01 to 5,000 mm
Accepted: 0.0001 to 500 m
Accepted: 3.6E-6 to 3,600,000 kg/h
Accepted: 0.01 to 2,000 kg/m³
Accepted: 0.001 to 1,000 mPa·s
Accepted: 0.005 to 100 W/(m·K)
Accepted: 0.5 to 10 kJ/(kg·K)
Accepted: -73.15 to 726.85 °C
Accepted: -73.15 to 726.85 °C

Results

Turbulent: f = 0.0791 Re^−0.25 (1.0875 − 0.1125 α*) and Nu = 0.024 Re^0.8 Pr^0.4.

Constant wall temperature with the fluid as the only resistance (C* = 0, ε = 1 − e^(−NTU)); properties taken constant.

Aspect ratio 2b/2a1.0000
Hydraulic diameter70.710mm
Mass flux10.000kg/(m²·s)
Reynolds number34,919
Laminar fully developed f·Re (Fanning)14.230
Laminar Nusselt number, constant wall temperature2.9787
Laminar Nusselt number, constant axial heat flux3.6102
Fanning friction factor used0.005642
Nusselt number used89.755
Heat transfer coefficient36.938W/(m²·K)
Number of transfer units hA/(ṁc_p)1.0365
Effectiveness 1 − e^(−NTU)64.529%
Heat transfer rate2.3742kW
Outlet temperature74.106°C
Frictional pressure drop76.260Pa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Same flow in the square 70.71 mm duct. The inputs, in the units selected above:

InputValue
Long side of the duct70.710 mm
Short side of the duct70.710 mm
Duct length5.0000 m
Mass flow180.00 kg/h
Density1.0463 kg/m³
Viscosity0.020250 mPa·s
Thermal conductivity0.029100 W/(m·K)
Specific heat1.0080 kJ/(kg·K)
Inlet temperature27.000 °C
Wall temperature100.00 °C

Applying the formula below gives:

ResultValue
Aspect ratio 2b/2a1.0000
Hydraulic diameter70.710 mm
Mass flux10.000 kg/(m²·s)
Reynolds number34,919
Laminar fully developed f·Re (Fanning)14.230
Laminar Nusselt number, constant wall temperature2.9787
Laminar Nusselt number, constant axial heat flux3.6102
Fanning friction factor used0.005642
Nusselt number used89.755
Heat transfer coefficient36.938 W/(m²·K)
Number of transfer units hA/(ṁc_p)1.0365
Effectiveness 1 − e^(−NTU)64.529 %
Heat transfer rate2.3742 kW
Outlet temperature74.106 °C
Frictional pressure drop76.260 Pa

Open this example in the calculator and change any input.

Formula

\(D_h = \frac{4ab}{a + b}, \quad f\,Re = 24\left(1 - 1.3553\alpha^* + 1.9467\alpha^{*2} - 1.7012\alpha^{*3} + 0.9564\alpha^{*4} - 0.2537\alpha^{*5}\right)\)

\(Nu_T = 7.541\left(1 - 2.610\alpha^* + 4.970\alpha^{*2} - 5.119\alpha^{*3} + 2.702\alpha^{*4} - 0.548\alpha^{*5}\right), \quad \varepsilon = 1 - e^{-NTU}, \quad \Delta p = \frac{4fLG^2}{2\rho D_h}\)

Variables

Symbol Meaning SI unit
\(2a\) Long side of the duct m
\(2b\) Short side of the duct m
\(L\) Duct length m
\(\dot m\) Mass flow kg/s
\(\rho\) Density kg/m³
\(\mu\) Viscosity Pa·s
\(k\) Thermal conductivity W/(m·K)
\(c_p\) Specific heat J/(kg·K)
\(T_i\) Inlet temperature K
\(T_w\) Wall temperature K
\(\alpha^*\) Aspect ratio 2b/2a -
\(D_h\) Hydraulic diameter m
\(G\) Mass flux kg/(m²·s)
\(Re\) Reynolds number -
\(f\,Re\) Laminar fully developed f·Re (Fanning) -
\(Nu_T\) Laminar Nusselt number, constant wall temperature -
\(Nu_{H1}\) Laminar Nusselt number, constant axial heat flux -
\(f\) Fanning friction factor used -
\(Nu\) Nusselt number used -
\(h\) Heat transfer coefficient W/(m²·K)
\(NTU\) Number of transfer units hA/(ṁc_p) -
\(\varepsilon\) Effectiveness 1 − e^(−NTU) -
\(q\) Heat transfer rate W
\(T_o\) Outlet temperature K
\(\Delta p\) Frictional pressure drop Pa

Method and standards

Laminar fully developed fits by Shah and London and turbulent rectangular-duct correlations, with the ε–NTU relation for C* = 0.

Where it is used

  • Air and gas ducts heated by steam or hot walls.
  • Microchannel and plate-fin passages.
  • Choosing a duct aspect ratio.

Common mistakes

  • Using the long side alone instead of the hydraulic diameter.
  • Applying fully developed laminar values to a short duct.

Assumptions and limits

  • Smooth ducts, constant properties, no entrance effects.

Questions and answers

Why does a flat duct transfer more heat than a square one of the same area?

Its perimeter is larger and its hydraulic diameter smaller, so both h and the wetted area rise; the pressure drop rises faster still (Shah's example: 1.30 × heat for 1.97 × pressure drop).

Which laminar Nusselt number applies?

Nu_T for a uniform wall temperature (condensing steam outside); Nu_H1 for uniform heat flux along the duct with a uniform perimeter temperature (electric heating, counterflow with equal capacity rates).

What do the defaults represent?

An illustrative case: Same flow in the square 70.71 mm duct. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Shah and Sekulić, Fundamentals of Heat Exchanger Design (Wiley, 2003), Table 7.4 (Shah and London 1978 fits for f·Re, Nu_T and Nu_H1) and Example 7.5

Related calculators