Worked example
Example: Illustrative copper-water heat pipe, horizontal. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Liquid density | 975.00 kg/m³ |
| Surface tension | 64.000 mN/m |
| Latent heat | 2,310.0 kJ/kg |
| Liquid viscosity | 0.37000 mPa·s |
| Wick permeability | 1.5000e-04 mm² |
| Wick cross-sectional area | 20.000 mm² |
| Effective pore radius | 0.050000 mm |
| Effective length (L_a + (L_e + L_c)/2) | 250.00 mm |
| Total length | 350.00 mm |
| Tilt (evaporator above condenser positive) | 0 ° |
Applying the formula below gives:
| Result | Value |
|---|---|
| Maximum capillary pressure 2σ/r | 2,560.0 Pa |
| Adverse gravity head | 0 Pa |
| Capillary limit | 187.00 W |
| Liquid flow at the limit | 0.080951 g/s |
Open this example in the calculator and change any input.
Formula
\(\dot Q_{max} = \frac{\rho_l\sigma h_{fg}}{\mu_l}\frac{KA_w}{L_{eff}}\left(\frac{2}{r_{eff}} - \frac{\rho_lgL_t\sin\psi}{\sigma}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\rho_l\) | Liquid density | kg/m³ |
| \(\sigma\) | Surface tension | N/m |
| \(h_{fg}\) | Latent heat | J/kg |
| \(\mu_l\) | Liquid viscosity | Pa·s |
| \(K\) | Wick permeability | m² |
| \(A_w\) | Wick cross-sectional area | m² |
| \(r_{eff}\) | Effective pore radius | m |
| \(L_{eff}\) | Effective length (L_a + (L_e + L_c)/2) | m |
| \(L_t\) | Total length | m |
| \(\psi\) | Tilt (evaporator above condenser positive) | rad |
| \(\Delta p_{c}\) | Maximum capillary pressure 2σ/r | Pa |
| \(\Delta p_g\) | Adverse gravity head | Pa |
| \(\dot Q_{max}\) | Capillary limit | W |
| \(\dot m\) | Liquid flow at the limit | kg/s |
Method and standards
Capillary limit.
Where it is used
- Electronics and spacecraft thermal design.
- Choosing wick and fluid for heat pipes.
Common mistakes
- Ignoring tilt in the application orientation.
- Using the geometric pore size instead of the effective radius.
Assumptions and limits
- Vapour pressure drop neglected; uniform wick; properties at the operating temperature.
References
- Capillary limit of wicked heat pipes
Questions and answers
Why does tilting reduce the limit?
With the evaporator above the condenser, the wick must also lift the liquid against gravity.
What other limits exist?
Sonic, entrainment, boiling and viscous limits; the lowest one governs.
What do the defaults represent?
An illustrative copper–water heat pipe with a sintered wick (K = 1.5 × 10⁻¹⁰ m², r = 50 µm, 20 mm² wick area), horizontal, 350 mm long.