Worked example
Example: Laminar heavy oil 0.05 kg/s in 20 mm x 6 m, steam at 150 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tube inside diameter | 20.000 mm |
| Tube length | 6.0000 m |
| Flow | 180.00 kg/h |
| Specific heat | 2.0000 kJ/(kg·K) |
| Viscosity at the bulk temperature | 50.000 mPa·s |
| Thermal conductivity | 0.13000 W/(m·K) |
| Viscosity ratio bulk to wall (1 if unknown) | 0.40000 - |
| Inlet temperature | 40.000 °C |
| Wall temperature | 150.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reynolds number | 63.662 |
| Prandtl number | 769.23 |
| Film coefficient | 58.119 W/(m²·K) |
| hπDL/(ṁc_p) | 0.21910 |
| Outlet temperature | 61.644 °C |
| Heat transferred | 2.1644 kW |
| Log-mean temperature difference | 98.783 K |
Open this example in the calculator and change any input.
Formula
\(Nu = 0.027Re^{0.8}Pr^{1/3}\left(\frac{\mu}{\mu_w}\right)^{0.14}\ (\text{turbulent}), \quad Nu = 1.86\left(\frac{RePrD}{L}\right)^{1/3}\left(\frac{\mu}{\mu_w}\right)^{0.14}\ (\text{laminar})\)
\(T_2 = T_w - (T_w - T_1)\exp\left(-\frac{h\pi DL}{\dot mc_p}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Tube inside diameter | m |
| \(L\) | Tube length | m |
| \(\dot m\) | Flow | kg/s |
| \(c_p\) | Specific heat | J/(kg·K) |
| \(\mu\) | Viscosity at the bulk temperature | Pa·s |
| \(k\) | Thermal conductivity | W/(m·K) |
| \(\mu/\mu_w\) | Viscosity ratio bulk to wall (1 if unknown) | - |
| \(T_1\) | Inlet temperature | K |
| \(T_w\) | Wall temperature | K |
| \(Re\) | Reynolds number | - |
| \(Pr\) | Prandtl number | - |
| \(h\) | Film coefficient | W/(m²·K) |
| \(NTU\) | hπDL/(ṁc_p) | - |
| \(T_2\) | Outlet temperature | K |
| \(Q\) | Heat transferred | W |
| \(\Delta T_{lm}\) | Log-mean temperature difference | K |
Method and standards
Energy balance of a tube with a uniform wall temperature.
Where it is used
- Steam-traced or jacketed line heaters.
- Condensing-steam tube heaters.
Common mistakes
- Using the arithmetic mean temperature difference.
- Applying the turbulent equation in transition flow.
Assumptions and limits
- Constant properties and wall temperature.
Questions and answers
Why is no iteration needed?
With constant properties and a constant wall temperature the bulk temperature approaches the wall exponentially: T₂ = T_w − (T_w − T₁)e^(−NTU). Designers show the trial-and-error route reaching the same answer.
What is the viscosity ratio for?
Viscous oils heated at the wall flow more easily near it, raising h; cooling has the opposite effect.
What do the defaults represent?
An illustrative case: Laminar heavy oil 0.05 kg/s in 20 mm x 6 m, steam at 150 C. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 2.5, Example 2.6 (Sieder and Tate, 1936)