Worked example
Example: Cooling water fouling, R_inf 0.0003, tau 2,000 h, 6 months. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Asymptotic fouling resistance | 3.0000e-04 m²·K/W |
| Time constant (time to 63 % of the asymptote) | 2,000.0 h |
| Running time | 4,380.0 h |
| Clean overall coefficient | 1,500.0 W/(m²·K) |
| Fraction of the asymptote for the time question | 95.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fouling resistance after the running time | 2.6642e-04 m²·K/W |
| Share of the asymptote reached | 88.808 % |
| Fouled overall coefficient | 1,071.7 W/(m²·K) |
| Loss of overall coefficient | 28.553 % |
| Time to reach the chosen fraction | 5,991.5 h |
| Fully fouled overall coefficient | 1,034.5 W/(m²·K) |
Open this example in the calculator and change any input.
Formula
\(R_f(t) = R_{f,\infty}\left(1 - e^{-t/\tau_c}\right), \quad t_f = -\tau_c\ln(1 - f), \quad \frac{1}{U_f} = \frac{1}{U_c} + R_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R_{f,\infty}\) | Asymptotic fouling resistance | m²·K/W |
| \(\tau_c\) | Time constant (time to 63 % of the asymptote) | s |
| \(t\) | Running time | s |
| \(U_c\) | Clean overall coefficient | W/(m²·K) |
| \(f\) | Fraction of the asymptote for the time question | - |
| \(R_f(t)\) | Fouling resistance after the running time | m²·K/W |
| \(R_f/R_{f,\infty}\) | Share of the asymptote reached | - |
| \(U_f(t)\) | Fouled overall coefficient | W/(m²·K) |
| \(1 - U_f/U_c\) | Loss of overall coefficient | - |
| \(t_f\) | Time to reach the chosen fraction | s |
| \(U_{f,\infty}\) | Fully fouled overall coefficient | W/(m²·K) |
Method and standards
Asymptotic deposition–removal fouling model.
Where it is used
- Predicting exchanger performance between cleanings.
- Choosing a fouling allowance from operating data.
Common mistakes
- Designing on the full asymptotic resistance when cleaning is frequent.
- Assuming all fouling is asymptotic.
Assumptions and limits
- Constant operating conditions; no induction period.
Questions and answers
What does the time constant mean?
After one time constant the resistance reaches 63 % of its final value, after three about 95 %.
Which fouling follows this curve?
Particulate and some crystallisation fouling where the deposit erodes as it grows; chemical-reaction and corrosion fouling often grow linearly instead.
What do the defaults represent?
An illustrative case: Cooling water fouling, R_inf 0.0003, tau 2,000 h, 6 months. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Shah and Sekulić, Fundamentals of Heat Exchanger Design (Wiley, 2003), sec. 13.2.6, eqs. 13.11 to 13.13 and Example 13.1 (Kern and Seaton, 1959; Taborek et al., 1972)