Worked example
Example: Taste and odour 20,000 L/min, 0.05 to 0.01 mg/L. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow | 20,000 L/min |
| Initial concentration | 0.050000 mg/L |
| Target concentration | 0.010000 mg/L |
| Freundlich capacity (mg/g)(L/mg)^1/n | 40.000 - |
| Freundlich intensity 1/n | 0.40000 - |
| Carbon price per kg | 1.2000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Carbon loading at C_e | 6.3396 g/kg |
| Carbon dose | 6.3096 mg/L |
| Carbon used | 181.72 kg/d |
| Annual carbon cost | 79,591 |
Open this example in the calculator and change any input.
Formula
\(q_e = K_fC_e^{1/n}, \quad \frac{m}{V} = \frac{C_o - C_e}{q_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow | m³/s |
| \(C_o\) | Initial concentration | kg/m³ |
| \(C_e\) | Target concentration | kg/m³ |
| \(K_f\) | Freundlich capacity (mg/g)(L/mg)^1/n | - |
| \(1/n\) | Freundlich intensity 1/n | - |
| \(c_{PAC}\) | Carbon price per kg | - |
| \(q_e\) | Carbon loading at C_e | kg/kg |
| \(m/V\) | Carbon dose | kg/m³ |
| \(\dot m\) | Carbon used | kg/s |
| \(C_a\) | Annual carbon cost | - |
Method and standards
Freundlich isotherm with a batch mass balance.
Where it is used
- Taste, odour and micropollutant control.
- Comparing PAC and GAC.
Common mistakes
- Using q_e at the influent concentration.
- Isotherm units in mg/g with concentrations in g/m³ mixed up.
Assumptions and limits
- Equilibrium reached; isotherm valid at C_e.
Questions and answers
Why is the capacity taken at the final concentration?
In a mixed contactor all the carbon ends in contact with the treated water, so it can load only to q_e(C_e).
How can less carbon be used?
Two-stage countercurrent contact or a granular carbon column loads the carbon nearer to the influent concentration.
What do the defaults represent?
An illustrative case: Taste and odour 20,000 L/min, 0.05 to 0.01 mg/L. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 11-9, eq. 11-54 and Example 11-14