Worked example
Example: Same with 0.06 mm copper fins. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Plate spacing (fin height) | 24.000 mm |
| Fin thickness | 0.060000 mm |
| Fin density | 15.240 1/in |
| Heat transfer coefficient | 170.00 W/(m²·K) |
| Fin thermal conductivity | 401.00 W/(m·K) |
| Fin material density | 8,933.0 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fin length, half the plate spacing | 12.000 mm |
| Fin parameter (2h/(k_fδ))^½ | 118.88 1/m |
| mℓ | 1.4265 |
| Fin efficiency | 62.457 % |
| Fin share of the total surface | 93.711 % |
| Overall surface efficiency | 64.818 % |
| Heat transfer area per unit flow length and width | 30.656 |
| Fin mass per square metre of passage plan area | 7.7181 kg/m² |
Open this example in the calculator and change any input.
Formula
\(\eta_f = \frac{\tanh(m\ell)}{m\ell}, \quad m = \left(\frac{2h}{k_f\delta}\right)^{1/2}, \quad \ell = \frac{b}{2}\)
\(\eta_o = 1 - \frac{A_f}{A}(1 - \eta_f)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(b\) | Plate spacing (fin height) | m |
| \(\delta\) | Fin thickness | m |
| \(n_f\) | Fin density | 1/m |
| \(h\) | Heat transfer coefficient | W/(m²·K) |
| \(k_f\) | Fin thermal conductivity | W/(m·K) |
| \(\rho_f\) | Fin material density | kg/m³ |
| \(\ell\) | Fin length, half the plate spacing | m |
| \(m\) | Fin parameter (2h/(k_fδ))^½ | 1/m |
| \(m\ell\) | mℓ | - |
| \(\eta_f\) | Fin efficiency | - |
| \(A_f/A\) | Fin share of the total surface | - |
| \(\eta_o\) | Overall surface efficiency | - |
| \(A/W\) | Heat transfer area per unit flow length and width | - |
| \(m_{fin}\) | Fin mass per square metre of passage plan area | kg/m² |
Method and standards
Straight rectangular fin with an adiabatic tip and the overall surface efficiency of a finned passage.
Where it is used
- Plate-fin (brazed aluminium) exchangers.
- Choosing fin thickness, density and material.
Common mistakes
- Using the full plate spacing as the fin length.
- Applying η_f to the whole surface instead of η_o.
Assumptions and limits
- Uniform h; one-dimensional conduction in the fin.
Questions and answers
Why is the fin length half the plate spacing?
Both plates are heated (or cooled) equally, so the fin's mid-height is a line of symmetry with no heat flow, just like the tip of a fin of length b/2.
Copper or aluminium?
Aluminium has 59 % of copper's conductivity, so η_f drops (0.76 to 0.66 in Shah's example), but the fins weigh less than a third as much.
What do the defaults represent?
An illustrative case: Same with 0.06 mm copper fins. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Shah and Sekulić, Fundamentals of Heat Exchanger Design (Wiley, 2003), sec. 4.3, eqs. 4.134 and 4.158 and Example 4.3