Worked example
Example: Water at 1 atm in a 25 mm tube, 500 kg/(m2 s), x = 0.05, 8 K superheat. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mass flux | 500.00 kg/(m²·s) |
| Tube inside diameter | 25.000 mm |
| Vapour mass fraction (quality) | 5.0000 % |
| Wall superheat T_w − T_sat | 8.0000 K |
| P_sat(T_w) − P_sat(T_sat) | 46.600 kPa |
| Pressure | 101.33 kPa |
| Critical pressure | 22,064 kPa |
| Molar mass | 18.015 kg/kmol |
| Liquid density | 958.40 kg/m³ |
| Vapour density | 0.59800 kg/m³ |
| Liquid viscosity | 0.28200 mPa·s |
| Vapour viscosity | 0.012300 mPa·s |
| Liquid thermal conductivity | 0.67900 W/(m·K) |
| Liquid specific heat | 4.2160 kJ/(kg·K) |
| Surface tension | 58.900 mN/m |
| Latent heat | 2,257.0 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Liquid-alone Reynolds number | 42,110 |
| Liquid Prandtl number | 1.7510 |
| Liquid-alone coefficient (Dittus–Boelter) | 3,912.7 W/(m²·K) |
| Lockhart–Martinelli parameter | 0.48360 |
| Chen enhancement factor | 4.3114 |
| Chen suppression factor | 0.15342 |
| Forster–Zuber nucleate coefficient | 8,646.6 W/(m²·K) |
| Chen coefficient (Forster–Zuber) | 18,196 W/(m²·K) |
| Chen coefficient with Mostinski–Palen nucleate term | 18,151 W/(m²·K) |
| Heat flux, Chen–Mostinski | 145.21 kW/m² |
| Liu–Winterton enhancement factor | 5.6555 |
| Liu–Winterton suppression factor | 0.73565 |
| Liu–Winterton coefficient | 24,747 W/(m²·K) |
| Heat flux, Liu–Winterton | 197.98 kW/m² |
Open this example in the calculator and change any input.
Formula
\(h_b = S_{CH}h_{nb} + F(X_{tt})h_L, \quad F = 2.35\left(X_{tt}^{-1} + 0.213\right)^{0.736}, \quad S_{CH} = \left[1 + 2.53\times10^{-6}(Re_LF^{1.25})^{1.17}\right]^{-1}\)
\(h_{b,LW} = \left[(S_{LW}h_{nb})^2 + (E_{LW}h_L)^2\right]^{1/2}, \quad E_{LW} = \left[1 + xPr_L\frac{\rho_L - \rho_V}{\rho_V}\right]^{0.35}, \quad S_{LW} = \left(1 + 0.055E_{LW}^{0.1}Re_L^{0.16}\right)^{-1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(G\) | Mass flux | kg/(m²·s) |
| \(D_i\) | Tube inside diameter | m |
| \(x\) | Vapour mass fraction (quality) | - |
| \(\Delta T_e\) | Wall superheat T_w − T_sat | K |
| \(\Delta P_{sat}\) | P_sat(T_w) − P_sat(T_sat) | Pa |
| \(P\) | Pressure | Pa |
| \(P_c\) | Critical pressure | Pa |
| \(M\) | Molar mass | kg/kmol |
| \(\rho_L\) | Liquid density | kg/m³ |
| \(\rho_V\) | Vapour density | kg/m³ |
| \(\mu_L\) | Liquid viscosity | Pa·s |
| \(\mu_V\) | Vapour viscosity | Pa·s |
| \(k_L\) | Liquid thermal conductivity | W/(m·K) |
| \(c_{p,L}\) | Liquid specific heat | J/(kg·K) |
| \(\sigma\) | Surface tension | N/m |
| \(\lambda\) | Latent heat | J/kg |
| \(Re_L\) | Liquid-alone Reynolds number | - |
| \(Pr_L\) | Liquid Prandtl number | - |
| \(h_L\) | Liquid-alone coefficient (Dittus–Boelter) | W/(m²·K) |
| \(X_{tt}\) | Lockhart–Martinelli parameter | - |
| \(F(X_{tt})\) | Chen enhancement factor | - |
| \(S_{CH}\) | Chen suppression factor | - |
| \(h_{nb,FZ}\) | Forster–Zuber nucleate coefficient | W/(m²·K) |
| \(h_b\) | Chen coefficient (Forster–Zuber) | W/(m²·K) |
| \(h_b'\) | Chen coefficient with Mostinski–Palen nucleate term | W/(m²·K) |
| \(\hat q'\) | Heat flux, Chen–Mostinski | W/m² |
| \(E_{LW}\) | Liu–Winterton enhancement factor | - |
| \(S_{LW}\) | Liu–Winterton suppression factor | - |
| \(h_{b,LW}\) | Liu–Winterton coefficient | W/(m²·K) |
| \(\hat q_{LW}\) | Heat flux, Liu–Winterton | W/m² |
Method and standards
Superposition and asymptotic models of convective plus nucleate boiling in tubes.
Where it is used
- Thermosyphon and forced-circulation reboilers.
- Evaporator tube design.
Common mistakes
- Using the total flow in Re_L.
- Using the pool-boiling form of Mostinski (fixed ΔT) inside Chen, which must be solved with the flow-boiling heat flux.
Assumptions and limits
- Saturated boiling below dryout; vertical tubes.
Questions and answers
Why is the Liu–Winterton result so much higher?
Its nucleate term is Cooper's correlation, which predicts far more nucleate boiling than Forster–Zuber or Mostinski for this fluid.
What do the defaults represent?
An illustrative case: Water at 1 atm in a 25 mm tube, 500 kg/(m2 s), x = 0.05, 8 K superheat. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 9.5, eqs. 9.68 to 9.82 and Example 9.7 (Chen 1966; Liu and Winterton 1991)