Worked example
Example: Virus credit, 1 mg/L, 0.2/min, 3 x 4 min, t10/t 0.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ozone residual leaving the first compartment | 1.0000 mg/L |
| Ozone decay rate | 0.20000 1/min |
| Detention time of each compartment | 4.0000 min |
| Reaction compartments after the first | 3.0000 - |
| Baffling factor t10/t | 50.000 % |
| Coefficient of specific lethality (base 10, L/(mg·min)) | 1.6000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| CT of the reaction compartments | 1.4839 |
| Log inactivation | 2.3742 |
| Residual leaving the last compartment | 0.090718 mg/L |
Open this example in the calculator and change any input.
Formula
\(C_i = C_1e^{-k\,t_c\,i}, \quad CT = \sum_{i=1}^{n}C_i\,t_c\frac{t_{10}}{t}, \quad \log\frac{N_o}{N} = \Lambda\cdot CT\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_1\) | Ozone residual leaving the first compartment | kg/m³ |
| \(k\) | Ozone decay rate | 1/s |
| \(t_c\) | Detention time of each compartment | s |
| \(n\) | Reaction compartments after the first | - |
| \(t_{10}/t\) | Baffling factor t10/t | - |
| \(\Lambda\) | Coefficient of specific lethality (base 10, L/(mg·min)) | - |
| \(CT\) | CT of the reaction compartments | - |
| \(\log(N_o/N)\) | Log inactivation | - |
| \(C_n\) | Residual leaving the last compartment | kg/m³ |
Method and standards
Ozone CT by compartments with first-order decay.
Where it is used
- Ozone disinfection design for reuse.
- Checking log credits.
Common mistakes
- Counting the first (demand) compartment.
- Using t instead of t10.
Assumptions and limits
- First-order ozone decay; Chick-Watson inactivation.
Questions and answers
Why multiply by t10/t?
Regulatory CT credit uses t10, the time by which 10 % of a tracer has passed, to allow for short-circuiting; 0.6 is typical of a well-baffled over-under contactor.
What do the defaults represent?
An illustrative case: Virus credit, 1 mg/L, 0.2/min, 3 x 4 min, t10/t 0.5. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 12-7, eq. 12-6 and Example 12-10