Worked example
Example: Same suspension at 1.2 m/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Overflow rate (critical velocity) | 1.2000 m/h |
| Width of each velocity class | 0.50000 m/h |
| Particles in class 1 (lowest velocities) | 30.000 - |
| Particles in class 2 | 50.000 - |
| Particles in class 3 | 90.000 - |
| Particles in class 4 | 110.00 - |
| Particles in class 5 | 100.00 - |
| Particles in class 6 | 70.000 - |
| Particles in class 7 | 30.000 - |
| Particles in class 8 | 20.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fraction of particles removed | 91.500 % |
| Particles in | 500.00 |
| Particles removed | 457.50 |
| Particles remaining in the effluent | 42.500 |
Open this example in the calculator and change any input.
Formula
\(R = \frac{\sum_i \min\!\left(1, \dfrac{v_{n_i}}{v_c}\right)n_i}{\sum_i n_i}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(v_c\) | Overflow rate (critical velocity) | m/s |
| \(\Delta v\) | Width of each velocity class | m/s |
| \(n_1\) | Particles in class 1 (lowest velocities) | - |
| \(n_2\) | Particles in class 2 | - |
| \(n_3\) | Particles in class 3 | - |
| \(n_4\) | Particles in class 4 | - |
| \(n_5\) | Particles in class 5 | - |
| \(n_6\) | Particles in class 6 | - |
| \(n_7\) | Particles in class 7 | - |
| \(n_8\) | Particles in class 8 | - |
| \(R\) | Fraction of particles removed | - |
| \(\sum n_i\) | Particles in | - |
| \(\sum n_r\) | Particles removed | - |
| \(\sum n_e\) | Particles remaining in the effluent | - |
Method and standards
Ideal (Hazen) settling basin for discrete particles.
Where it is used
- Interpreting settling-column tests.
- Choosing an overflow rate.
Common mistakes
- Using the upper class limit instead of the mid-point.
- Applying it to flocculent suspensions, which need isopercent curves.
Assumptions and limits
- Discrete, non-flocculating particles; quiescent ideal basin.
Questions and answers
Why does depth not appear?
In an ideal basin a particle is removed if its settling velocity exceeds the overflow rate Q/A; depth cancels out, which is why surface area governs clarifier design.
Can I use mass instead of particle numbers?
Yes: enter the mass (or percentage) in each velocity class and the result is the fraction of mass removed.
What do the defaults represent?
An illustrative case: Same suspension at 1.2 m/h. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Metcalf and Eddy (Tchobanoglous, Stensel, Tsuchihashi and Burton), Wastewater Engineering: Treatment and Resource Recovery, 5th ed. (McGraw-Hill, 2014), sec. 5-4, eq. 5-30 and Example 5-5